APPENDIX E: BOILER DEFAULT SETTINGS
Page
120
of
158
PR2: 04/22/13
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
Operation and Maintenance Manual
OMM-0052_0E
GF-127
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
•
Ph: 800-526-0288
Table E-1: Boiler Default Settings (Continued)
MENU & OPTION
FACTORY DEFAULT
Configuration Menu --
Continued
Network Timeout
30 seconds
Hi DB Setpt En
30
Demand Offset
10
Deadband High
2
Deadband Low
2
Tuning Menu
Prop Band
70°F
Integral Gain
1.00
Derivative Time
0.0 min