APPENDIX D: INDOOR/OUTDOOR RESET RATIO CHARTS
Page
118
of
158
PR2: 04/22/13
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
Operation and Maintenance Manual
OMM-0052_0E
GF-127
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
•
Ph: 800-526-0288
Table D-7. Header Temperature for a Building Reference Temperature of 90F
RESET RATIO
Air
Temp
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
2.4
90F
90
90
90
90
90
90
90
90
90
90
85F
93
94
95
96
97
98
99
100
101
102
80F
96
98
100
102
104
106
108
110
112
114
75F
99
102
105
108
111
114
117
120
123
126
70F
102
106
110
114
118
122
126
130
134
138
65F
105
110
115
120
125
130
135
140
145
150
60F
108
114
120
126
132
138
144
150
156
162
55F
111
118
125
132
139
146
153
160
167
174
50F
114
122
130
138
146
154
162
170
178
186
45F
117
126
135
144
153
162
171
180
189
198
40F
120
130
140
150
160
170
180
190
200
210
35F
123
134
145
156
167
178
189
200
30F
126
138
150
162
174
186
198
210
25F
129
142
155
168
181
194
207
20F
132
146
160
174
188
202
216
15F
135
150
165
180
195
210
10F
138
154
170
186
202
218
5F
141
158
175
192
209
0F
144
162
180
198
216