APPENDIX K
K-1
BENCHMARK DUAL-FUEL
PROPANE SWITCH-OVER INSTRUCTIONS
Prior to operating a Benchmark Dual-Fuel Unit using propane, the Start and Stop levels must be
changed to 28% and 24%. In addition, the following valves must be set to the following
positions:
•
The Diverter Valve handle shown in Figure 1 must be set to the PROPANE (UP) position.
•
The Air Injection Valve handle shown in Figure 2 must be set to the Open position.
START/STOP LEVEL CHANGES
The Start and Stop levels are changed using the front panel controls on the C-More Control
Box. Proceed as follows:
1. Press the
MENU
key once.
Setup Menu
will be displayed.
2. Press the
▲
arrow key once.
Password
will be displayed.
3. Press the
CHANGE
key.
Password
will begin to flash.
4. Using the
▲
arrow key, increment the display and stop at
6817.
5. Press the
ENTER
key to store the displayed password.
6.
Password 2
will be displayed, indicating that the valid Level 2 password has been
stored.
7. Next, access the
Calibration Menu
by pressing the
MENU
key four times.
8. Press the
▼
arrow key one time.
Start Level 20%
should be displayed indicating that it
is currently set for Natural Gas operation.
9. Press the
CHANGE
key. The
Start Level
will begin to flash.
10. Press the
▲
arrow key and increase the
Start Level
to
28%.
11. Press the
ENTER
key to store the
28% Start Level.
12. Press the
▼
arrow key again.
Stop Level 16%
should be displayed indicating that it is
currently set for Natural Gas operation.
13. Press the
CHANGE
key. The
Stop Level
will begin to flash.
14. Press the
▲
arrow key and increase the
Stop Level
to
24%.
15. Press the
ENTER
key to store the
24% Stop Level.
16. Return to the
Operating Menu
by pressing the
BACK
key twice.
17. Refer to Figure 1 and verify that the Diverter Valve handle is set to the PROPANE (UP)
position.
18. Refer to Figure 2 and verify that the Air Injection Valve is Open
IMPORTANT
Remember to change the Start/Stop Levels back to 20% and 16%
prior to switching back to Natural Gas operation. Also, ensure that
the Diverter Valve handle is properly positioned as shown in
Figure 1 and the Air Injection Valve shown in Figure 2 is Closed.
Summary of Contents for AERCO Benchmark 2.0
Page 30: ......
Page 38: ......
Page 44: ......
Page 50: ......
Page 56: ......
Page 66: ...APPENDIX C C 1 Temperature Sensor Resistance Chart Balco...
Page 76: ...APPENDIX F F 5...
Page 80: ...APPENDIX F F 9...
Page 81: ...APPENDIX F F 10...
Page 86: ...APPENDIX G G 7...