APPENDIX I
I-1
RECOMMENDED PERIODIC TESTING CHECK LIST
WARNING
NOTE: Periodic testing of all boiler controls and safety devices is required to determine that they are operating as
designed. Precautions shall be taken while tests are being performed to protect against bodily injury and property
damage. The owner or user of an automatic boiler system should set up a formal system of periodic preventive
maintenance and testing. Tests should be conducted on a regular basis and the results recorded in a log-book.
Item
Frequency Accomplished
by
Remarks
See indicated sections of this manual for detailed procedures
Gages, monitors and
indicators
Daily
Operator
Make visual inspection and record readings in
operator log
Instrument and
equipment settings
Daily
Make visual check against factory recommended
specifications
Weekly
Operator
Verify factory settings
Firing rate control
Semiannually
Service
technician
Verify factory settings
Annually
Service
technician
Check with combustion test equipment- see
section 7.4
flue, vent, stack or
intake air duct
monthly
Operator
Visual inspection for condition or obstructions
Igniter
Weekly
Operator
see section 7.2
main fuel valve
valve position
Weekly
Operator
Check position indicator
leakage test
annually
Service
technician
Close manual fuel supply valve and test for
pressure on down stream valve port
Combustion safety
flame failure
weekly
Operator
Close manual fuel supply valve check safety
shutdown timing
flame signal strength
weekly
Operator
Read signal with meter and log see section 7.3
low water fuel cut off
and alarm
weekly
operator
See section 6.3
slow drain test
Semiannually
operator
Perform a slow drain test in accordance with
ASME Boiler and Pressure
Vessel Code section IV
high limit safety control
test
annually
Service
technician
See section 6.4
operating control
annually
Operator
See section 3.2
low air pressure
monthly
Operator
See section 6.6
high and low gas
pressure interlocks
monthly
Operator
See section 6.2
air valve purge position
switch
annually
Service
technician
See section 6.6
low fire position switch
Annually
Service
technician
See section 6.7
safety valves
as required
Operator
As per A.S.M.E. Boiler and Pressure Vessel
Code section IV
inspect burner
components
Semiannually
Service
technician
See section 7.6
Summary of Contents for AERCO Benchmark 2.0
Page 30: ......
Page 38: ......
Page 44: ......
Page 50: ......
Page 56: ......
Page 66: ...APPENDIX C C 1 Temperature Sensor Resistance Chart Balco...
Page 76: ...APPENDIX F F 5...
Page 80: ...APPENDIX F F 9...
Page 81: ...APPENDIX F F 10...
Page 86: ...APPENDIX G G 7...