background image

Operation & Maintenance Manual 

AquaSolve

®

Page 7 of 8

Replacing the Media

1.  Shut off the primary water supply going to the 

AquaSolve tank.

2.  Open up a downstream spigot or faucet to release 

pressure in the tank and in the distribution lines 
before and after the system.

3.  Close the inlet and outlet isolation valves immedi-

ately before and after the tank.

4.  Place into By-Pass position, remove bypass clips 

and then disconnect bypass from head.

5.  Using a step ladder and strap wrench, remove 

the threaded head assembly connection (turning 
counter-clockwise) and remove the complete upper 
assembly including the screen attached to the bot-
tom of the head assembly. Rinse these parts in a 
nearby sink or bucket of water. Do not drain the 
tank.

6.  Remove the distributor tube with the bottom strain-

er. Rinse these parts in a nearby sink or bucket of 
water.

7.  Get a 6ft length of 3/4” sch. 40 PVC and a length 

of 1” polyvinyl hose. The length of hose depends 
on the distance to the nearest floor drain. (Both of 
these can be acquired at a local hardware store).

8.  Insert one end of the pipe inside the hose and put 

the other end of the pipe into the top of the tank 
and down into the media. Put the other end of the 
hose inside a rice bag and put the rice bag on the 
floor drain.

9.  Get a garden hose and put it on the open end of 

the poly hose to fill the hose and pipe with water. 
Air will bubble out of the tank. Once all the air is 
out of the hose and pipe, you can start a siphon to 
remove the media. Put the garden hose in the top 
of the tank and turn it on to keep the tank full of 
water. Push the pipe up and down in the media to 
get it all out. The rice bag will catch the media and 
allow the water to go down the drain.

10.  Try not to be too aggressive when extracting the 

media. You need to take it out in small bites. If you 
let the whole pipe/ hose fill with media it will plug 
up. You need to let slugs of water flush out the pipe 
as you go.

11.  When all the old media is removed turn off the gar-

den hose and continue to siphon until the tank is 

Your AquaSolve media should be replaced every 3 years. Dispose 
of old media and/or container in accordance with local, regional, 
national, and/or international regulations.

NOTICE

about half full with water.

12.  Reinstall the distributer tube with bottom strainer 

that was removed in step 6. Center the distributor 
tube in the bottom of the tank, making sure the 
distributor tube is flush with the top of the tank. 
Keeping any and all media from entering the distrib-
utor tube, cap the top open end of the distributor 
tube with plastic sheeting and tape. Test it to make 
sure it will not come off during the media loading 
process. Carefully pour-in a new bag of media that 
specifically meets the replacement requirement 
of the tank. For example, an AM8408-COM sys-
tem requires (x1) AM8408-COM-RM Replacement 
Media.

13.  Inspect the threaded connection on the top of the 

tank to ensure no loose beads of media are stuck 
to the internal threads. If visible, wipe away the 
beads with a damp cloth, then remove the plastic 
sheeting and tape from the top of the distributor 
tube.

14.  Re-attach the head assembly onto the distributor 

tube and thread the head assembly back onto 
the tank. Fully hand tighten the head to the tank, 
reconnect the bypass to the head and reinstall the 
bypass clips. Insure the Coupling O-rings are not 
pinched.

15.  Turn on the primary water supply and slowly place 

AquaSolve By-Pass Valve into Service position (see 
image on page 6 for reference).

16.  Slowly open the outlet isolation valve and slightly 

open the inlet isolation valve to allow water to flow 
into the system and out of a downstream cold side 
faucet to purge the air from the tank and plumbing 
system.

17.  Once the tank is full of  

water, wait 4 hours for  
media to “hydrate”.

18.  Fully open the inlet isolation  

valve and the system is now  
ready for operation.

Technical Support

  •  (800) 526-0288  •  Mon-Fri, 8 am - 5 pm EST

OMM-0155-AquaSolve-AM8408-AM8410

Summary of Contents for AERCO AquaSolve AM8408-COM

Page 1: ...g this equipment Failure to read and follow all safety and use information can result in death serious personal injury property damage or damage to the equipment Keep this Manual for future reference 2021 AERCO AERCO International Inc 100 Oritani Drive Blauvelt NY 10913 USA T 845 580 8000 Toll Free 800 526 0288 AERCO com Technical Support 800 526 0288 Mon Fri 8 am 5 pm EST Heating and Hot Water So...

Page 2: ... a water softener for the prevention of scale due to water hardness Virtually maintenance free no control valve Uses environmentally friendly technology by using no salt or other chemicals to constantly add no electricity and no wastewater Improves efficiency of all water using appliances both hot and cold Simple sizing and installation all you need to know is pipe size and the peak flow rate Safe...

Page 3: ...h other forms of water treatment 1 AquaSolve must be the last stage in the treatment chain Do not install any filters after AquaSolve or before any devices for which scale prevention is required POU filters e g carbon RO or Ultraviolet UV are exempt from this requirement 2 Do not apply any other antiscalants before or after AquaSolve 3 The addition of soaps chemicals or cleaners before or after Aq...

Page 4: ... the pipe and use a low corrosivity water soluble flux listed under the ASTM B813 standard AquaSolve media does not reduce silica scaling While silica tends to have a less significant effect on scale formation than other minerals it can act as a binder that makes water spots and scale residue outside the plumbing system difficult to remove This 20 ppm limitation is for aesthetic purposes NOTICE Sy...

Page 5: ...the plumbing system must be supported by pipe hangers or other means NOTICE Install Piping Connect the inlet and outlet plumbing according to your preferences and any applicable local codes Include sample drain ports with hose bibb connec tions on the inlet and outlet piping to facilitate startup and service Check the head on top of the tank It s common for it to loosen during shipment Tighten the...

Page 6: ...arance of these objects protect remove them or use the outlet hose to drain option 7 Connect the outlet of the AquaSolve system to the cold water supply to the building Install an outlet valve user supplied in this line and close it 8 Slowly fully open the outlet and supply valves to the AquaSolve system 9 Open hot and cold faucets downstream from the AquaSolve system to relieve any air from the p...

Page 7: ...You need to let slugs of water flush out the pipe as you go 11 When all the old media is removed turn off the gar den hose and continue to siphon until the tank is Your AquaSolve media should be replaced every 3 years Dispose of old media and or container in accordance with local regional national and or international regulations NOTICE about half full with water 12 Reinstall the distributer tube ...

Page 8: ...earest factory at no cost excluding freight and local labor charges if any Damage to the media due to chlorine other oxidizers or fouling caused by local water conditions or any other operation outside of the limits shown under Specifications is not cov ered by this warranty The warranty set forth herein is given expressly and is the only war ranty given by AERCO Company with respect to the produc...

Reviews: