NOTE
An operator cannot manually close a boiler valve using the BVC if that
particular boiler is firing.
3.6
IMPORTANT NOTES
The following should be noted before reading the remainder of this manual.
•
The AERCO Boiler Valve Controller operates independently from the AERCO Boiler
Management System.
•
The five buttons labeled F1 through F5 appearing below the touch screen are not
operational.
•
If a boiler is firing, the corresponding valve cannot be manually moved to the “CLOSED”
position to avoid temperature overshoot.
•
The factory default setting for the time delay is two minutes. The user may subsequently
set the time delay in minute increments from one to thirty.
•
It is not recommended to lower the time delay below the two minute factory default
setting except for the purposes of servicing.
•
Any time delay that is set will universally apply to all of the valves.
•
To trigger the action of a touch screen button, tap the middle of the circular area
representing the button.