background image

6

Test Procedures

Reduced Pressure Zone Assemblies must be inspected and
tested periodically, in accordance with local codes, to ensure
proper operation of check valves within the unit.

A differential pressure gauge is recommended for Test No. 1
rather than a manometer for the following reasons: It utilizes
minimum time to perform the test. It eliminates the necessity of
closing the inlet ball valve which could release pipe scale and
foreign matter into the backflow preventer. Only a slight amount
of water is ‘spilled’ in test. A mercury manometer could cause a
pollution hazard.

Test Set Up
Reduced Pressure Zone Assembly

Close Valves A, B and C on Test Kit.
Connect high side hose to test cock #2
Connect low side hose to test cock #3. Close shutoff #2.
Open test cocks #2 and #3.
Open vent valve C.
Open ‘high’ valve A and bleed to atmosphere until all the 
air is expelled.
Close valve A. Open ‘low’ valve B and bleed to atmosphere until
all air is expelled. Close ‘low’ valve B. Close ‘vent’ valve C.
Connect vent hose to test cock #4.

Test Procedure
Reduced Pressure Zone Assembly

Field Test Equipment Required

Watts Test Kit

Test No. 1

Purpose:

To test Check Valve No. 2 for tightness against reverse

flow.
Requirements: Valve must be tight against reverse flow under all
pressure differentials. Slowly open the ‘high’ valve A and the
‘vent’ valve C, and keep the ‘low’ valve B closed. Open test
cock #4. Indicated pressure differential will decrease slightly. If
pressure differential continues to decrease (until the vent opens)
check valve #2 is reported as ‘leaking’.

Test No. 2

Purpose:

To test shutoff #2 for tightness.

Requirements: After passing Test No. 1, continue to Test No. 2
by closing test cock #2. The indicated pressure differential will
decrease slightly. If pressure differential continues to decrease
(approaching “zero”), shutoff #2 is reported to be “leaking”.

Test No. 3

Purpose:

To test Check Valve No. 1 for tightness.

Requirements: Valve must be tight against reverse flow under all
pressure differentials. Close ‘high’ valve A and open test cock
#2. Close test cock #4. Disconnect vent hose at test cock #4.
Open valves B and C, bleeding to atmosphere. Then closing
valve B restores the system to a normal static condition.
Observe the pressure differential gauge. If there is a decrease in
the indicated value, Check Valve No. 1 is reported as “leaking”.

Test No. 4

Purpose:

To test operation of pressure differential relief valve.

Requirements: The pressure differential relief valve must operate
to maintain the “zone” between the two check valves at least 2
psi (14 kPa) less than the supply pressure. Close ‘vent’ valve C.
Open ‘high’ valve A. Open the ‘low’ valve B very slowly until the
differential gauge needle starts to drop. Hold the valve at this
position and observe the gauge reading at the moment the first
discharge is noted from the relief valve. Record this as the open-
ing differential pressure of the relief valve.
Note: It is important that the differential gauge needle drops
slowly.
Close test cocks #2 and #3. Use ‘vent’ hose to relieve pressure
from test kit by opening valves A, B and C. Remove all test
equipment and open shutoff #2.

Strainer

Test Cock

No. 1

Test Cock

No. 2

High Hose 

(Color - Yellow)

Auxiliary

Test Cock

Ball Type 

(A) Test Valves (C)

(B)

Needle

Valve

Test Cock

No. 3

Test Cock

No. 4

Shutoff

No. 2

Relief

Valve

Low Hose 

(Color - White or Red)

Vent Hose 

(Color - Blue)

919QTS

Summary of Contents for 919 Series

Page 1: ...HANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE Any implied warranties that are imposed by law are limited in duration to one year Some States do not allow limitations on how long an implied warranty lasts and some States do not allow the exclusion or limitation of incidental or consequential damages Therefore the above limi tations may not apply to you This Limited Warranty gives you specific leg...

Page 2: ... system or sump 2 Do not install the Series 919 in any location where any part of the unit could become submerged in standing water Parallel Installation For parallel installations you can install two or more small sized Series 919 s when approved to serve a large supply pipe main You can use this type of installation in an application where increased capacity beyond that provided by a single valv...

Page 3: ... when 1 the first check valve is fouled or 2 the inlet pressure to the check valve drops sufficiently due to upstream pres sure fluctuations This then affects the required operating differential between the inlet pressure and the reduced pressure zone or 3 the second check is fouled during emergency backflow or resulting from a water hammer condition For troubleshooting guide send for literature S...

Page 4: ...eat back into the chamber bore 13 Slide the diaphragm assembly into the relief valve seat 14 Place the spring on to the diaphragm assembly 15 Place the cover O ring on the diaphragm assembly 16 Line up the grooves on the relief valve cover with the grooves in the relief valve body and turn the cover clockwise 1 4 turn to seat the cover 17 Using a wrench place the bolts back into the cover and tigh...

Page 5: ...ghten the cover using the appropriate sized wrench 13 Service the second check valve using Steps 2 through 12 14 Slowly open shutoff valves ORDER CODE KIT NO SIZE in mm 1st Check Kits 0888110 RK 919 CK1 1 4 1 2 8 15 0888111 RK 919 CK1 3 4 20 0888112 RK 919 CK1 1 25 0888113 RK 919 CK1 11 4 11 2 32 40 0888114 RK 919 CK1 2 50 Kit consists of Check Assembly Spring and Cover O ring 2nd Check Kits 08881...

Page 6: ... shutoff 2 for tightness Requirements After passing Test No 1 continue to Test No 2 by closing test cock 2 The indicated pressure differential will decrease slightly If pressure differential continues to decrease approaching zero shutoff 2 is reported to be leaking Test No 3 Purpose To test Check Valve No 1 for tightness Requirements Valve must be tight against reverse flow under all pressure diff...

Page 7: ...7 NOTES ...

Page 8: ...06 USA 815 Chestnut St No Andover MA 01845 6098 www watts com Canada 5435 North Service Rd Burlington ONT L7L 5H7 www wattscanada ca W a t e r S a f e t y F l o w C o n t r o l P r o d u c t s For additional information visit our web site at www watts com ...

Reviews: