background image

5

Servicing First & Second Check Valves 

1

4

" – 2" (8 – 50mm)

NOTES

: 1. No special tools are required to service the Series 919 

1

4

" - 2" (8 – 50).

2. Before servicing, make sure the water is turned off or

shutoff valves are closed.

1.

Close shutoff valves up and downstream of the valve.

2.

Using an appropriate sized wrench, loosen the check valve
cover. Unscrew the check valve cover and lift it off.

3.

Remove the spring.

4.

Lift out the disc holder assembly from the body of the valve.

5.

To reverse the seat disc, unscrew the disc screw and disassemble
the disc washer and disc rubber from the disc holder assembly.
Reverse the disc rubber so the opposite face is showing. 

6.

Assemble the disc screw through the disc washer and 
disc rubber, and screw it into the disc holder.

7.

To replace the seat module, pull the seat module 
out of the body by gripping at the reinforcement 
ring. Replace the seat module with the new seat 
by placing it into the body seat bore.

NOTE:

When you tighten the cover in Step 12, the 

cover will engage the seat module properly.

8.

Insert the disc holder assembly back into the seat module.

9.

Replace the spring ensuring that it seats properly on the 
disc holder.

WA R N I N G

The first check valve has a heavy weight spring. The second check
valve has a lighter weight spring. When reassembling the check
valves, make sure you install the correct spring into the correct
check valve.

10.

Place the cover onto the spring with the internal guide on the
cover positioned inside the end coil.

11.

Screw the cover onto the valve body.

12.

Tighten the cover using the appropriate sized wrench.

13.

Service the second check valve using Steps 2 through 12.

14.

Slowly open shutoff valves.

ORDER CODE

KIT NO.

SIZE

in.

mm

1st Check Kits: 

0888110

RK 919 CK1 

1

4

– 

1

2

8 – 15

0888111

RK 919 CK1 

3

4

20

0888112

RK 919 CK1 

1

25

0888113

RK 919 CK1 

1

1

4

– 1

1

2

32 – 40

0888114

RK 919 CK1 

2

50

Kit consists of: Check Assembly, Spring and Cover O-ring

2nd Check Kits: 

0888115

RK 919 CK2 

1

4

– 

1

2

8 – 15

0888116

RK 919 CK2 

3

4

20

0888117

RK 919 CK2 

1

25

0888118

RK 919 CK2 

1

1

4

– 1

1

2

32 – 40

0888119

RK 919 CK2 

2

50

Kit consists of: Check Assembly, Spring and Cover O-ring

1st or 2nd Check Rubber Parts Kits: 

0888120

RK 919 RC4

1

4

– 

1

2

8 – 15

0888121

RK 919 RC4

3

4

20

0888122

RK 919 RC4

1

25

0888123

RK 919 RC4

1

1

4

–1

1

2

32 – 40

0888124

RK 919 RC4 

2

50

Kit consists of: Disc, Seat O-ring and Cover O-ring

ORDER CODE

KIT NO.

SIZE

in.

mm

Check Seat Kits: 

0888125

RK 919 S

1

4

– 

1

2

8 – 15

0888126

RK 919 S

3

4

20

0888127

RK 919 S 

1

25

0888128

RK 919 S

1

1

4

– 1

1

2

32 – 40

0888129

RK 919 S 

2

50

Kit consists of: Seat, Seat O-ring and Cover O-ring

Complete Valve Rubber Parts Kits:

0888140

RK 919 RT

1

4

– 

1

2

8 – 15

0888141

RK 919 RT

3

4

20

0888142

RK 919 RT

1

25

0888143

RK 919 RT

1

1

4

– 1

1

2

32 – 40

0888144

RK 919 RT 

2

50

Kit consists of: 2 Check Discs, 2 Check Seat O-rings, 1 RV Disc

Check Cover Kits: 

0888145

RK 919 C

1

4

– 

1

2

8 – 15

0888146

RK 919 C

3

4

20

0888147

RK 919 C

1

25

0888148

RK 919 C

1

1

4

– 1

1

2

32 – 40

0888149

RK 919 C

2

50

Kit consists of: Cover and Cover O-ring

Replacement Parts 

1

4

" – 2" (8 – 50mm)

When ordering, specify Ordering Code Number, Kit Number and Valve Size.

Check Disc Washer

Check Disc Screw

Check Seat

Check Seat

O-ring

Cover

Cover O-ring

Check Spring

Check Disc Rubber

Check Disc Holder

Check Assembly

Summary of Contents for 919 Series

Page 1: ...HANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE Any implied warranties that are imposed by law are limited in duration to one year Some States do not allow limitations on how long an implied warranty lasts and some States do not allow the exclusion or limitation of incidental or consequential damages Therefore the above limi tations may not apply to you This Limited Warranty gives you specific leg...

Page 2: ... system or sump 2 Do not install the Series 919 in any location where any part of the unit could become submerged in standing water Parallel Installation For parallel installations you can install two or more small sized Series 919 s when approved to serve a large supply pipe main You can use this type of installation in an application where increased capacity beyond that provided by a single valv...

Page 3: ... when 1 the first check valve is fouled or 2 the inlet pressure to the check valve drops sufficiently due to upstream pres sure fluctuations This then affects the required operating differential between the inlet pressure and the reduced pressure zone or 3 the second check is fouled during emergency backflow or resulting from a water hammer condition For troubleshooting guide send for literature S...

Page 4: ...eat back into the chamber bore 13 Slide the diaphragm assembly into the relief valve seat 14 Place the spring on to the diaphragm assembly 15 Place the cover O ring on the diaphragm assembly 16 Line up the grooves on the relief valve cover with the grooves in the relief valve body and turn the cover clockwise 1 4 turn to seat the cover 17 Using a wrench place the bolts back into the cover and tigh...

Page 5: ...ghten the cover using the appropriate sized wrench 13 Service the second check valve using Steps 2 through 12 14 Slowly open shutoff valves ORDER CODE KIT NO SIZE in mm 1st Check Kits 0888110 RK 919 CK1 1 4 1 2 8 15 0888111 RK 919 CK1 3 4 20 0888112 RK 919 CK1 1 25 0888113 RK 919 CK1 11 4 11 2 32 40 0888114 RK 919 CK1 2 50 Kit consists of Check Assembly Spring and Cover O ring 2nd Check Kits 08881...

Page 6: ... shutoff 2 for tightness Requirements After passing Test No 1 continue to Test No 2 by closing test cock 2 The indicated pressure differential will decrease slightly If pressure differential continues to decrease approaching zero shutoff 2 is reported to be leaking Test No 3 Purpose To test Check Valve No 1 for tightness Requirements Valve must be tight against reverse flow under all pressure diff...

Page 7: ...7 NOTES ...

Page 8: ...06 USA 815 Chestnut St No Andover MA 01845 6098 www watts com Canada 5435 North Service Rd Burlington ONT L7L 5H7 www wattscanada ca W a t e r S a f e t y F l o w C o n t r o l P r o d u c t s For additional information visit our web site at www watts com ...

Reviews: