background image

2

Basic Installation Instructions

1

4

" – 2" (8 – 50mm)

Series 919 Reduced Pressure Zone Assemblies

Air Gap

Strainer

Indoor Installation

For indoor installations, make sure the Series 919 is easily
accessible to facilitate testing and servicing. Do not install in
concealed locations. If the location of the Series 919 is parallel
and close to the wall, make sure the test cocks are easily
accessible, and the drain line can adequately drain if required.
An air gap and drain line (see literature ES-AG/EL/TC) are piped
from the relief valve connection as shown, allowing evidence of
discharge to be clearly visible and preventing the occurrence of
water damage. 

Outdoor, Above Ground Installation

For outdoor installations, it is recommended that you install the
Series 919AQT where there are no freezing conditions and
above ground whenever possible.
You must install the Series 919 in an accessible location to 
facilitate testing and servicing. The installation must also allow
for adequate drainage from the air gap and the discharge line 
if needed. 

WA R N I N G

1. Do not allow the drain line to empty directly into a drainage

ditch, sewer system, or sump. 

2. Do not install the Series 919 in any location where any part

of the unit could become submerged in standing water. 

Parallel Installation

For parallel installations, you can install two or more small sized
Series 919's (when approved) to serve a large supply pipe main.
You can use this type of installation in an application where
increased capacity beyond that provided by a single valve is
required. Additionally, this type of installation permits testing
and/or servicing of a single valve without shutting down the
complete line.
The number of Series 919 units installed in parallel should be
determined by the engineer's judgement, based on the operating
conditions of a specific application.

NOTE:

The total capacity of all the units installed in the application

should equal or exceed that required by the system.

Now available, WattsBox Insulated Enclosures,

for more information, send for literature ES-WB.

FIBERGLASS WattsBox

Min. 12"

Annual inspection of all water system safety and control valves 
is required and necessary. Regular inspection, testing and 
cleaning assures maximum life and proper product function.

Meter

Indoor Installation

Outdoor Installation

Parallel Installation

12" (300mm) Minimum

(refer to local codes)

Watts

1

4

" – 2" (8 – 50mm) 919

Watts

1

4

" – 2" 

(8 – 50mm)

919AQT

Watts

1

4

" – 2" 919

(8 – 50mm)

Min. 12" (300mm)

Summary of Contents for 919 Series

Page 1: ...HANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE Any implied warranties that are imposed by law are limited in duration to one year Some States do not allow limitations on how long an implied warranty lasts and some States do not allow the exclusion or limitation of incidental or consequential damages Therefore the above limi tations may not apply to you This Limited Warranty gives you specific leg...

Page 2: ... system or sump 2 Do not install the Series 919 in any location where any part of the unit could become submerged in standing water Parallel Installation For parallel installations you can install two or more small sized Series 919 s when approved to serve a large supply pipe main You can use this type of installation in an application where increased capacity beyond that provided by a single valv...

Page 3: ... when 1 the first check valve is fouled or 2 the inlet pressure to the check valve drops sufficiently due to upstream pres sure fluctuations This then affects the required operating differential between the inlet pressure and the reduced pressure zone or 3 the second check is fouled during emergency backflow or resulting from a water hammer condition For troubleshooting guide send for literature S...

Page 4: ...eat back into the chamber bore 13 Slide the diaphragm assembly into the relief valve seat 14 Place the spring on to the diaphragm assembly 15 Place the cover O ring on the diaphragm assembly 16 Line up the grooves on the relief valve cover with the grooves in the relief valve body and turn the cover clockwise 1 4 turn to seat the cover 17 Using a wrench place the bolts back into the cover and tigh...

Page 5: ...ghten the cover using the appropriate sized wrench 13 Service the second check valve using Steps 2 through 12 14 Slowly open shutoff valves ORDER CODE KIT NO SIZE in mm 1st Check Kits 0888110 RK 919 CK1 1 4 1 2 8 15 0888111 RK 919 CK1 3 4 20 0888112 RK 919 CK1 1 25 0888113 RK 919 CK1 11 4 11 2 32 40 0888114 RK 919 CK1 2 50 Kit consists of Check Assembly Spring and Cover O ring 2nd Check Kits 08881...

Page 6: ... shutoff 2 for tightness Requirements After passing Test No 1 continue to Test No 2 by closing test cock 2 The indicated pressure differential will decrease slightly If pressure differential continues to decrease approaching zero shutoff 2 is reported to be leaking Test No 3 Purpose To test Check Valve No 1 for tightness Requirements Valve must be tight against reverse flow under all pressure diff...

Page 7: ...7 NOTES ...

Page 8: ...06 USA 815 Chestnut St No Andover MA 01845 6098 www watts com Canada 5435 North Service Rd Burlington ONT L7L 5H7 www wattscanada ca W a t e r S a f e t y F l o w C o n t r o l P r o d u c t s For additional information visit our web site at www watts com ...

Reviews: