REV. 01 - OCTOBER 2020 - BLÜCHER
®
CONNECTED ROOF
29
…
…
1
diagnostic sensor signal
1
uint16
0 ... 40
13901
…
…
16
diagnostic sensor signal
16
uint16
0 ... 40
13916
…
…
1
diagnostic internal leak
1
uint16
0 ... 255
14001
…
…
16
diagnostic internal leak
16
uint16
0 ... 255
14016
…
…
1
diagnostic water level 1
1
uint16
0 ... 255
14101
…
…
16
diagnostic water level 1
16
uint16
0 ... 255
14116
…
…
1
diagnostic water level 2
1
uint16
0 ... 255
14201
…
…
16
diagnostic water level 2
16
uint16
0 ... 255
14216
…
…
1
diagnostic water level 3
1
uint16
0 ... 255
14301
…
…
16
diagnostic water level 3
16
uint16
0 ... 255
14316
…
…
1
diagnostic water level 4
1
uint16
0 ... 255
14401
…
…
16
diagnostic water level 4
16
uint16
0 ... 255
14416
…
…
1
diagnostic water level 5
1
uint16
0 ... 255
14501
…
…
16
diagnostic water level 5
16
uint16
0 ... 255
14516
…
…
1
diagnostic battery voltage
1
uint8, x20 and decimal place
= 3
0 ... 4.000 V
14601
0-7
…
…
16
diagnostic battery voltage
16
uint8, x20 and decimal place
= 3
0 ... 4.000 V
14616
0-7
…
…
1
diagnostic battery voltage min
1
uint8, x20 and decimal place
= 3
0 ... 4.000 V
14701
0-7
…
…
16
diagnostic battery voltage min
16
uint8, x20 and decimal place
= 3
0 ... 4.000 V
14716
0-7
…
…
1
diagnostic error counter
1
uint16
14801
…
…
16
diagnostic error counter
16
uint16
14816
…
…
1
diagnostic CTN temperature
1
uint16
-35.0 ... 85.0 °C
14901
…
…
16
diagnostic CTN temperature
16
uint16
-35.0 ... 85.0 °C
14916
…
…
1
clear communication lost alarm
1
bool
holding
register
R/W
16
15001
0
clear blocked sensor alarm
bool
15001
1
clear blocked drain alarm
bool
15001
2
clear battery low alarm
bool
15001
3
clear internal leak alarm
bool
15001
4
…
…
16
clear communication lost alarm
16
bool
15016
0
clear blocked sensor alarm
bool
15016
1
clear blocked drain alarm
bool
15016
2
clear battery low alarm
bool
15016
3
clear internal leak alarm
bool
15016
4
1 modbus address structure:
Xnnnn -> 0 - “parameters combined by monitor index number” group, 1 - “parameters combined by type” group
nXXnn -> monitor index number
nnnXX -> parameter index number for a monitor
2 version numbers are represented by “A.B” format - each letter is a single byte