RoomResponse

TM

 Signal

The RoomResponse

TM

 signal adjusts the temperature of 

a modulating condensing boiler that accepts a 0-10 V(dc) 

or 4-20 mA input. It works by continually adjusting boiler 

water temperatures to the lowest possible value to meet 

comfort without wasting energy. This is done by monitoring 

each thermostat's on and off time pattern and determines 

the ideal water temperature for each zone. The control 

then chooses the highest water temperature requirement 

of all the thermostats and provides a 0-10 V (dc) or 4-20 

mA signal proportional to the boiler operating temperature. 

The RoomResponse

TM

 signal is a DOE compliant method 

of controlling boiler temperature to building load. The 

RoomResponse

TM

 signal is not available to on/off boilers. 

Benefits of the RoomResponse

TM

 signal include:

•  Increase in boiler efficiency

•  Reduction in room temperature swing
•  Reduction in expansion noises from heating pipes

Mod Max % Dial

The upper limit of the 0-10 V (dc) or 4 -20 mA signal to 
the modulating condensing boiler can be set using the 
Mod Max % Dial.
This sets the upper temperature limit for the boiler.
The dial is only applicable to controls set as the Master.

Mod Max %

Max Voltage

Max mA

50

5

12

60

6

13.6

70

7

15.2

80

8

16.8

90

9

18.4

100

10

20

FUSE 6

70 80

90

60

50

100

MOD MAX %

Mod Max % dial set to 100% in the illustration.

Boiler Make/Model

Required Adapter

(Supplied by boiler 

manufacturer)

0-10 V (dc) /

4-20 mA

DIP Switch

Mod Max % Dial for Boiler Design Temperature

120°F

140°F

160°F

180°F

Aerco AM series

Not required

0-10 V

50%

65%

80%

100%

Bosch Greenstar

ICM Module

0-10 V

55%

70%

80%

100%

Buderus GB142, GB162

EM10 Module

0-10 V

50%

60%

75%

90%

Burnham

®

 Alpine

*

Not required

4-20 mA

50%

70%

85%

100%

Camus

®

 Modulating Micoflame

®

Not required

0-10 V

50%

60%

70%

85%

HTP Elite

Not required

0-10 V

50%

65%

80%

90%

IBC VFC and SL series

*

Not required

0-10 V

65%

75%

85%

100%

Laars

®

 Mascot LX

Not required

0-10 V

55%

70%

85%

100%

Laars

®

 Mascot FT

Not required

0-10 V

50%

65%

80%

100%

Lochinvar

®

 Knight

Not required

0-10 V

55%

70%

85%

100%

Lochinvar

®

 FTXL

*

Not required

0-10 V

55%

70%

85%

100%

NTI Trinity Fire Tube and LX

Not required

4-20 mA

55%

65%

75%

90%

Peerless PureFire

PFA-1 Adapter

0-10 V

55%

65%

75%

90%

Raypak Xfyre, Xtherm, MVB, XPakFT

Not required

0-10 V

55%

65%

80%

90%

Riverside HeatStation

*

Not required

0-10 V

50%

65%

85%

100%

Viessmann 100-W, WB1B

OpenTherm Module

0-10 V

55%

70%

85%

100%

Viessmann 200-W, B2HB and 300 CU3A

Not required

0-10 V

50%

60%

70%

80%

Weil-McLain

®

 Evergreen

*

Not required

0-10 V

50%

70%

85%

100%

* Requires changes to boiler's settings

Setting the Max Mod % Dial

Expansion Terminals

•  Connect the five wires of the expansion bus from the 

master to the member controls.

Terminal Description

A/tN4

Away signal connecting tekmar thermostats

B

RoomResponse

TM 

signal from member controls

C

Power common

D

Demand signal. 0 Vdc = demand. 2 Vdc = no 

demand

E

Priority signal. 0 Vdc = priority. 2 Vdc = no priority 

Summary of Contents for 779655030518

Page 1: ...culator and zone valves to provide heating to a zoned hydronic heating system RoomResponseTM signal Compatible with all low voltage thermostats Unlimited zone expansion Zone priority Priority override...

Page 2: ...if not avoided could result in minor or moderate injury This symbol identifies practices actions or failure to act which could result in property damage or damage to the equipment Read manual and all...

Page 3: ...eedle nose pliers Wire stripper 18 AWG LVT solid wire low voltage connections 14 AWG solid wire line voltage connections Four 1 8 1 wood screws 1 Zone Valve Control 305V 2 Spare fuses located in cover...

Page 4: ...lle d whe n u s i n g p o w e r stealing thermostats e g Thermostat T4 N B1 PS 305V V1 V2 V3 V4 V5 Away C R Rh W Away C R Rh W Away C R Rh W R W R W MOD X X tN4 T1 T2 T3 T4 T5 T6 A DHW C R W BOILER T...

Page 5: ...aling Thermostat T4 Generic Bi Metallic Strip Thermostat V1 2 Wire Zone Valve V2 3 Wire Zone Valves e g Taco 570 V3 V4 4 Wire Zone Valve Away C R Rh W Away C R Rh W R W R W MOD X X tN4 T1 T2 T3 T4 T5...

Page 6: ...ay C R Rh W Away C R Rh W T T Away C R Rh W MOD X X tN4 T1 T2 T3 T4 T5 T6 A DHW C R W BOILER T STAT 1 T STAT 2 T STAT 3 tN4 A C R W tN4 A C R W T STAT 4 tN4 A C R W T STAT 5 tN4 A C R W T STAT 6 EXPAN...

Page 7: ...he boiler If using a single Switching Relay set to Master When using multiple Switching Relays and or Zone Valve Controls set one control to Master and set all other controls to Member The boiler end...

Page 8: ...ration Boiler Make Model Required Adapter Supplied by boiler manufacturer 0 10 V dc 4 20 mA DIP Switch Mod Max Dial for Boiler Design Temperature 120 F 140 F 160 F 180 F Aerco AM series Not required 0...

Page 9: ...Change Energy Management setting Central Heat Modulation Source to 4 20 mA Change Energy Management setting Central Heat 4 20 mA Setup 4 mA Water Temperature to 80 F 26 5 C 9 10 22 23 5 6 16 17 2 U 1...

Page 10: ...tpoint source to 4 20mA Enter boiler password Set Parameter Setpoint source to 4 20mA Lochinvar Knight Lochinvar FTXL NTI Trinity LX Riverside HeatStation NTI Trinity Fire Tube 305V 305V 305V 305V 305...

Page 11: ...305V 305V 1 4 1 2 5 6 Connect to the Viessmann Extension Module EA1 Plug 0 10V Zone Valve Control 305V Five Zones with Priority Literature Submittal 305V_C Installation Manual 305V_D Job Record 305V_...

Page 12: ...made by Pur chaser to its customers which are different from or in excess of the tekmar Limited Warranty are the Purchaser s sole responsibility and obligation Purchaser shall indemnify and hold tekma...

Reviews: