10
CONTROL PROGRAMMING
DIR/TIME CLOCK
OPTIONS
For DIR Softeners, there are two
options for setting the Gallons
Capacity. The Gallons Capacity
is automatically calculated if set
to AUTO. Reserve Capacity, is
automatically estimated based on water usage if AUTO is used.
The other option is to set the Gallons Capacity to a specific
number. If a specific number is set, reserve capacity is zero,
unless the value is manually set (i.e. the manufacturer inten-
tionally sets the gallon capacity number below the calculated
capacity of the system).
This control valve is set up in the AUTO mode; it can also be set
to regenerate immediately or at the next regeneration time by
changing the Regeneration Time Option. There arc three choic-
es for settings:
1.
“NORMAL” means regeneration will occur at the pre
set regeneration time.
2.
“On 0” means regeneration will occur when the gallons
capacity reaches zero.
3.
“NORMAL” and “on 0” means the regeneration will occur at
the preset regeneration time unless the gallons capacity
reaches zero. If the gallon capacity reaches zero, the
regeneration will begin 10 minutes after no water usage.
The user can initiate manual regeneration. The user has the option
to request the manual regeneration at the delayed regeneration
time or to have the regeneration occur immediately:
1.
Pressing and releasing the REGEN button. “Regen t o d a y ”
will flash on the display and the regeneration will occur at
the delayed regeneration time. The user can cancel the
request by pressing and releasing the REGEN button. This
method of manually initiating regeneration is not allowed
when the system is set to immediately regenerate when the
capacity reaches
zero.
2.
Pressing and holding the REGEN button for approximately
3 seconds will immediately start the regeneration. The user
cannot cancel this request, except by resetting the control
by pressing NEXT and REGEN buttons simultaneously for
3 seconds.
FACTORY DEFAULT
PROGRAMMING
To change p
ress
and hold
NEXT
&
▼
1
. Configuration . . . . . . . . . . . . . . . . . . . . .Softener
2
. Grain Capacity . . . . . . . . . . . . . . . . . . . . . . . . .*
3.
Pounds of salt per regeneration . . . . . . . . . . . .*
4.
Backwash Duration . . . . . . . . . . . . . . . . .Normal
5.
Gallons Capacity . . . . . . . . . . . . . . . . . . . . .Auto
6.
Brine Refill . . . . . . . . . . . . . . . . . . . . . . . . . .Pre
7.
Regenerant Flow . . . . . . . . . . . . . . . . . . . . . .dn
8.
Regeneration Initiation . . . . . . . . . . .0
Installer Setup:
Press
NEXT
&
▲
1.
Hardness . . . . . . . . . . . . . . . . . . . . . . . .“grains”
2.
Calendar Override . . . . . . . . . . . . . . . . . . . . . . .
3.
Time of Regeneratiuon (hour) . . . . . . . .
2
:00AM
4.
Time of Regeneratiuon (minute) . . . . . .2:
00
AM
Diagnostics:
Press
▼
&
▲
1.
Number of days since last regeneration
2.
Number of gallons since last regeneration
3.
Reserve capacity gallons used in last 7 days
4.
Daily gallon usage for last 64 days
5.
Current flow rate
6.
Maximum flow rate in the last seven days
7.
Total gallons since the last reset
8.
Number of days since last reset
9.
Number of regenerations since the last reset
Valve History:
Press
▼
&
▲
then
▼
&
▲
1.
Software version
2.
Maximum
flow rate since start-up
3.
Total number of gallons since start-up
4.
Total number of days since start-up
5.
Total Number of regenerations since start-up
6.
Number of error occurences since start-up
* Refer to specification table 2 page 4.
FILTER
SETTINGS*
DIR
SOFTENER
REGENERANT
RESERVE CAPACITY
TIME
CLOCK
BACKWASH
ONLY
DAY
OVERRIDE
GALLON
CAPACITY
Yes
Automatically Calculated Yes Off Auto
Yes
Off
Auto
Yes
If desired enter a value less
Yes
Yes
Yes
Off
Any Number
than estimated capacity
Yes
Yes
Automatically calculated
Yes
Any Number
Auto
Yes
Yes
If desired enter a value less
Yes
Yes
Yes
Any Number
Any Number
than estimated capacity
Yes None Yes
Yes
Yes
Any
Number
Off
* Day override AND Gallon Capacity cannot be set to "off" at the same time
Figure 15: Key Pad