Section 2
Auto-Zone CV & CV-EX
2-12
Installation and Wiring
CV System Sensors
Room Sensors
The Room Sensor uses a patented flush mount design to isolate the temperature sensing
element from the housing which mounts flush with the wall surface.
Room Sensors should be located on an inside wall away from direct sunlight or heat
producing equipment such as computers, copiers, etc. Such devices can adversely affect
the accuracy of the sensor. Although the sensor eliminates most of the effects of thermal
coupling to the walls, try to avoid walls which retain large amounts of thermal energy
(such as marble or steel). Walls containing either cold or warm air currents should also be
avoided whenever possible. Avoid locating the sensor in dead air areas of a room. This
will result in slow response to temperature changes in the space.
Figure 2-8:
Room Sensor Installation
Mount the sensor approximately 50-60 inches from the floor for best results. The Room
Sensor is designed to mount vertically in a standard 2 by 4 inch electrical box. The sensor
may be mounted directly into the drywall where electrical codes do not require low
voltage wiring to be enclosed in conduit. A template is supplied with the sensor to
facilitate cutting a hole of the correct size.
firealarmresources.com
Summary of Contents for Auto-Zone CV
Page 1: ...Design Installation And Operations Manual CV CV EX System Revision 01B firealarmresources com...
Page 2: ...firealarmresources com...
Page 4: ...firealarmresources com...
Page 6: ...firealarmresources com...
Page 12: ...firealarmresources com...
Page 38: ...firealarmresources com...
Page 102: ...Section 4 Auto Zone CV CV EX 4 36 Start Up and Troubleshooting Notes firealarmresources com...
Page 103: ...firealarmresources com...