Auto-Zone CV & CV-EX
Section 3
Programming
3-3
Main User Menu
View/Change Zone
1) View/Change Zone
2) View Alarms
MENU) Full Access
ESC) Main Screen
1)
View/Change
Zone
For quick access to an individual
zone, select this menu item. Any
Constant Volume unit can be
selected. The user can view the room
temperature and change the current
cooling and heating setpoints. You
must be at least a Level 1 user to
change the setpoints.
2) View Alarms
If the System Manager has been
configured for Alarm Polling, the
user can select this item to get a list
of unit addresses that are currently in
alarm. If an alarm exists, the Alarm
LED will be active on the right side
of the panel.
MENU) Full
Access
If you are a Level 2 user, the full
system Read/Reset capabilities are
available to you. These capabilites
are accessed via this Menu button.
ESC) Main
Screen
When you have finished viewing the
system you can exit this menu and
return to the Main Screen by pressing
the ESC button..
View/Change
[ Enter Unit ID# ]
Selected Unit: 101
If you have selected the View/Change Zone menu item, you
will be allowed to view any selected zone temperature and its
current cooling and heating setpoints. If you are at least a Level
1 user, you can also change the cooling and heating setpoints
from this screen. The first screen that appears, prompts you for
the Unit ID you wish to view. For the CV system the Unit ID is
actually the address of the CV controller you assigned to each
board with the Address Switch. This would be a number
between 1 and 30. For the CV-EX system it would also be the
same CV controller address you assigned but it would be
preceded by the network loop address, which is the address
number (between 1 and 4) you set for the MiniLink whose loop
the particular CV controller resides on. For example the CV
controller address is 28 and it is on the loop with the MiniLink
addressed 2. The ID number you would enter would be 228.
firealarmresources.com
Summary of Contents for Auto-Zone CV
Page 1: ...Design Installation And Operations Manual CV CV EX System Revision 01B firealarmresources com...
Page 2: ...firealarmresources com...
Page 4: ...firealarmresources com...
Page 6: ...firealarmresources com...
Page 12: ...firealarmresources com...
Page 38: ...firealarmresources com...
Page 102: ...Section 4 Auto Zone CV CV EX 4 36 Start Up and Troubleshooting Notes firealarmresources com...
Page 103: ...firealarmresources com...