TROUBLESHOOTING

For any unexpected operation

1.  Check DIP switch settings.
2.  Make sure the switches are set according to the defined settings in the DIP 

Switch Setting chart.

Lights do not turn on when entering the room.

Neither LED Flashes 

1.  Check that the circuit breaker has been turned back on.
2.  Check all sensor and power pack wire connections.
3.  Check for 24VDC input to the sensor between the red and black low voltage 

wires.

• 

If 24VDC is present, replace the sensor.

• 

If 24VDC is not present, check the high voltage connections to the power 

pack.

• 

If high voltage connections are good and high voltage is present, replace 

the power pack.

Red LED does not flash 

1.  When power is initially applied to the sensor, there is a warm-up period of 30 

to 60 seconds before the LED becomes active.

2.  Make sure PIR sensitivity is set to 100% (DIP switch #5 is in the “off” position).

Green LED does not flash 

Ultrasonic sensitivity setting may need to be increased. Turn adjustment trimpot 

clockwise  until the LED begins to flash when movement occurs.

Green LED is on steady 

Check ultrasonic sensitivity trimpot. Fully counterclockwise position is the override 

for the sensor. Turn trimpot clockwise until LED flashes only when movement 

occurs in the desired coverage area.

CAUTION

TURN POWER OFF AT THE CIRCUIT BREAKER 

 

BEFORE WORKING WITH OR NEAR HIGH VOLTAGE.

Visit our website for FAQs: www.wattstopper.com

Summary of Contents for DT-200

Page 1: ...g Temperature 32 to 131 F 0 to 55 C Light Level One Step Adjustment 10FC to 200FC Time Delay Adjustment 30 seconds to 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 5 sec...

Page 2: ...nutes the lights are switched off A walk through mode can turn lights off after only 3 minutes if no activity is detected after 30 seconds of an occupancy detection The DT 200 operates on 24VDC suppli...

Page 3: ...erage patterns As a general rule each occupant should be able to clearly view the sensor Masking the PIR Lens Opaque adhesive tape is supplied so that sections of the PIR lens can be masked This restr...

Page 4: ...wire on sensor Wire from other side of switch to the red wire on sensor Wiring the Isolated Relay The Isolated Relay is rated for 1A 30VAC VDC Connect the wires necessary to the application that requ...

Page 5: ...osed Contact Orange Normally Open Contact Green Common Isolated Relay Outputs Grey Man Switch DT 200v3 Occupancy Sensor Grey wire on sensor is only used when connecting a manual momentary switch LVSW...

Page 6: ...racket so that it is in line with the half circle notch as illustrated in figure A Push the ball into the Base Bracket opening until it snaps into place being careful not to pinch the wires The bracke...

Page 7: ...htening Screw to hold this position Wall Mount PARALLEL to WALL at 10 foot mounting height Reference Surface Angle Ceiling Mount PARALLEL to VERTICAL at 10 foot mounting height Reference Surface Angle...

Page 8: ...ll not return it to previous settings If Test Mode is enabled after Light Level has been set Light Level functionality will cease to function throughout the duration of Test Mode When Test Mode period...

Page 9: ...or more resets the light to default maximum Press and hold the Light Level button for 5 seconds or until the detection LEDs turn ON and then OFF The LEDs flash rapidly for 10 seconds after the settin...

Page 10: ...re that the Ultrasonic Sensitivity trimpot is set to about 70 clockwise 4 Remain still The red and green LEDs should not flash The lights should turn off after 5 seconds If not see Troubleshooting 5 M...

Page 11: ...od that activates a change from Standby area unoccupied and loads are OFF to Occupied area occupied and loads are ON Both requires detection by PIR and Ultrasonic Either requires detection by only one...

Page 12: ...manual switch and it stays on according to the occupancy logic setting The time delay operates as programmed When the load turns OFF due to lack of occupancy detection it can be turned ON again by oc...

Page 13: ...h voltage is present replace the power pack Red LED does not flash 1 When power is initially applied to the sensor there is a warm up period of 30 to 60 seconds before the LED becomes active 2 Make su...

Page 14: ...corrected the sensor will return to normal operation Check the blue wire connection If necessary replace the power pack Lights do not turn off automatically Green LED flashes Reduce ultrasonic sensit...

Page 15: ...sensor to time out If lights turn off the sensor is working properly adjust sensitivity and time delay for the sensor If lights do not turn off check the wiring between the sensor and power pack If w...

Page 16: ...profit or cost of removal installation or reinstallation ORDERING INFORMATION Catalog Description DT 200 Dual Technology Occupancy Sensor Low Voltage w Isolated Relay DT 205 Dual Technology Occupancy...