Logic Configuration Chart
DIP SWITCH SETTING
Time Delay: Switches 1, 2, 3
The sensor will hold the lights ON as long as occupancy
is detected. The time delay countdown starts when no
motion is detected. After no motion is detected for the
length of the time delay, the sensor will turn the lights
OFF.
Walk-through: Switch 4
Walk-through mode turns the lights OFF three minutes
after the area is initially occupied, if no motion is
detected after the first 30 seconds. If motion continues
beyond the first 30 seconds, the selected time delay
applies.
PIR Sensitivity: switch 5
•
Minimum forces a reduced detection range for
the PIR.
•
Maximum causes the DT-200 to monitor the
controlled environment and automatically select
the maximum sensitivity that will provide reliable
operation without false detection. This setting is
constantly updated.
Occupancy Logic: Switches: 6, 7, 8
The DT-200 has 8 logic configurations for occupancy
triggers, set with DIP switches 6, 7 & 8. Determine the
appropriate Occupancy Logic Option using the Trigger
matrix, then set the DIP switches accordingly.
Initial Occupancy:
The method that activates a change
from “Standby” (area unoccupied and loads are
OFF
) to
“Occupied” (area occupied and loads are
ON
).
• Both
requires detection by PIR
and
Ultrasonic.
• Either
requires detection by only one technology.
• PIR
requires detection by the PIR.
• Man.
requires activation of the Manual
Switch. (See Manual
ON
functions” for further
information.)
Maintain Occupancy:
The method indicating that the
area is still occupied and the lights should remain
ON
.
Re-trigger:
After the time delay elapses and the lights
turn
OFF
, detection by the selected technology within
the number of seconds indicated turns the lights back
ON
.
Standard
Option 2
Option 3
Option 1
Trigger
Option 4
Option 5
Initial
Occupancy
Maintain Occupancy Re-trigger (seconds duration)
Occupancy Logic
Both
Both
PIR
Both(5)
Either(5)
Either
Either
Either
Either
Either(5)
Either(5)
Either
PIR
PIR
PIR
(5)
Either(30)
Either(5)
Either
= ON
= OFF
6 7 8
Standard
Option 2
Option 3
Option 1
Option 4
Option 5
Option 6
Option 7
Standard
Standard
Switch#
Occupancy
Logic
= Factory Setting
5 minutes
10 minutes
15 minutes
20 minutes
25 minutes
30 minutes
30 seconds
1 2 3
Time Delay
Test Mode/20 min
5
Minimum
PIR Sensitivity
Walk-Through
Enabled
Disabled
4
Maximum
PIR
PIR
Settings
Man.
Man. PIR Both(30)
Feature
Option 6
Option 7