D8 Series User’s Guide
Chapter 3: Communicating by DeviceNet
56
ATTRIBUTE
ACCESS
NAME
TYPE
DESCRIPTION
108 (6C hex)
Get/Set
Heat Filter
USINT
109 (6D hex)
Get/Set
Cool Filter
USINT
110 (6E hex)
Get/Set
Hysteresis
UINT
111 (6F hex)
Get/Set
Restore Automatic Mode
USINT
112 (70 hex)
Get/Set
Mode
USINT
NOTE!
All successful explicit message responses from a Set service will contain no data.
The response will be a two-byte message containing the requester’s node address and
service code (with R/R bit set).
Alarm Object
The Alarm Object provides read/write access to all alarm parameters. Instance 0 of this object
contains the class attributes listed in Table 3.26. The four-loop controller has four additional
instances, and the eight-loop controller has eight additional instances, each containing the attributes
listed in Table 3.27. Instance 1 corresponds to loop 1, instance 2 corresponds to loop 2, and so on.
Table 3.25
– Alarm Class and Services
Class Code
67 hex
Class Services
0E hex Get Attribute Single
Instance Services
0E hex Get Attribute Single
10 hex Set Attribute Single
Table 3.26
– Alarm Class Attributes (Instance 0)
ATTRIBUTE
ACCESS
NAME
TYPE
DESCRIPTION
1 (1 hex)
Get
Revision
UINT
Revision of this object
2 (2 hex)
Get
Max instance
UINT
Maximum instances of this object (8)
3 (3 hex)
Get
Number of instances
UINT
Number of object instances
Table 3.27
– Alarm Instance Attributes (Instances 1 to 4 or 8)
ATTRIBUTE
ACCESS
NAME
TYPE
DESCRIPTION
100 (64 hex)
Get/Set
Alarm High Set Point
INT
101 (65 hex)
Get/Set
Alarm Low Set Point
INT
102 (66 hex)
Get/Set
High Deviation Value
UINT
103 (67 hex)
Get/Set
Low Deviation Value
UINT
104 (68 hex)
Get/Set
Alarm Hysteresis
UINT
105 (69 hex)
Get/Set
Alarm High Output
USINT
106 (6A hex)
Get/Set
Alarm Low Output
USINT
107 (6B hex)
Get/Set
High Deviation Output
USINT
108 (6C hex)
Get/Set
Low Deviation Output
USINT
109 (6D hex)
Get/Set
Alarm Delay
UINT
110 (6E hex)
Get
Alarm Status
UINT