D8 Series User’s Guide
Chapter 6: Menu and Parameter Reference
110
Display Format
l
01 Disp format
r
b
-999to 3000
For a process input, choose the range and the number of decimal places for the process variable
and related parameters. Choose a precision appropriate for the range and accuracy of the sensor.
Values:
See Table 6.10
Default:
-999 to 3000
for a process input
DeviceNet™ Object:
Input (64 hex)
Table 6.10
– Display Formats
DISPLAY VALUE
DeviceNet™ VALUE
MINIMUM PROCESS
VARIABLE
MAXIMUM PROCESS
VARIABLE
-999 to 3000
255
-999
3000
-9999 to 30000
0
-9999
30000
-999.9 to 3000.0
1
-999.9
3000.0
-99.99 to 300.00
2
-99.99
300.00
-9.999 to 30.000
3
-9.999
30.000
-0.9999 to 3.0000
4
-0.9999
3.0000
Input Range High
l
01 Input range
r
high
b
1000 ˚F
For a process input, enter the high process variable for input scaling purposes. This value will be
displayed when the input signal is at the level set for
Input high signal
.
This parameter and the
Input high signal
parameter together define a point on the conversion line for
the scaling function. Setting Up a Process Input on page 69
Values:
Any value between
Input range low
and the maximum process variable for the selected
display format. See Table 6.10.
Default:
1000. Decimal placement depends upon the value of the
Disp format
parameter.
Decimal Placement for DeviceNet™:
Decimal Placement for Numeric Values on page 46
DeviceNet™ Object:
Input (64 hex)