Programming, Chapter 5
WATLOW Series 942 User's Manual
33
Program
Soak (SoAh) : The following parameters are associated with the soak step.
Hour:
The number of hours, in combination with the Min and SEC parameters,
equaling total step time to achieve the temperature under the SoAh step type. This
parameter only appears if PtYP = ti.
Range:
0 to 23
Default:
0
Minutes:
The number of minutes, in combination with the HOUr and SEC param-
eters, equaling total step time to achieve the temperature under the SoAh step
type. This parameter only appears if PtYP = ti.
Range:
0 to 59
Default:
0
Seconds:
The number of seconds, in combination with the HOUr and Min param-
eters, equaling total step time to achieve the temperature under the SoAh step
type. This parameter only appears if PtYP = ti.
Range:
0 to 59
Default:
0
Event 1:
Selects whether Event 1 is on or off. Only appears if Ot3 = Ent.
Range:
On or OFF
Default:
OFF
Event 2:
Selects whether Event 2 is on or off. Only appears if Ot4 = Ent.
Range:
On or OFF
Default:
OFF
Return:
Select no and you return to the StEP parameter to continue programming
the 942. By selecting YES, you exit the program menu and return to the control set
point.
Range:
YES or no
Default:
no
Jumploop Step (JL) : The following parameters are associated with the
jumploop step. When StEP = 1, JL will not appear.
Jump Step:
The Series 942 jumps backwards to any step in your file.
Range:
1 to 23
Default:
1
Jump Count:
The number of times the Series 942 jumps to the step specified by
the JS (jump step) parameter. 0 = infinite number of jumps.
Range:
0 to 100
Default:
0
Return:
Select no and you return to the StEP parameter to continue programming
the Series 942. By selecting YES, you exit the program menu and return to the
control set point.
Range:
YES or no
Default:
no
End Step (End) : The following parameters are associated with the end step.
End:
When HOLd is selected, the control and auxiliary outputs are enabled and
maintain the same state as in the last set point and/or soak step before the End
step was encountered. When selected as OFF, the control and auxiliary outputs
(except for deviation alarms) are de-energized and OFF is shown in the lower
display. When selected as OFFA, the control outputs are de-energized and OFF is
shown in the lower display. Deviation alarms are inactive (relay energized) and
process alarms are active (relay energized in non-alarm conditions).
Range:
HOLd or OFF
Default:
HOLd
Return:
Select no and you return to the StEP parameter to continue programming
the 942. By selecting YES, you exit the program menu and return to the control set
point.
Range:
YES or no
Default:
no
(SoAh)
HOUr
Min
SEC
Ent1
Ent2
rtn
(JL)
JS
JC
rtn
(End)
End
rtn