16
WATLOW Series 733/734 Service Manual
Setup Mode, Chapter 2
Parameter
Value
Range
Factory Default
Appears If:
C_F
C or F
F
gb
1 to 4000°F/2222°C
4000°F/2222°C
rtd
JIS or din
din
Input type is RTD
tncP
On or OFF
OFF
tS
hrnn or nnSc
nnSc
SIL
On or OFF
OFF
Unit has alarms,
AL1 no & AL2 no
LAt
LA or nL
nL
Unit has alarms,
AL1 no & AL2 no
InP1
J, K (appears as H), E or rtd
J or rtd
Dependent on model
number information
rL1
Sensor range low to rH1
Low limit sensor type
rH1
Sensor range high to rL1
High limit of sensor type
HYS1
1 to 99°F/1 to 55°C
3°F
AL1
Pr, dE or no
Pr
Unit has alarms
A1LO
If AL1 = dE: 0 to -999°F/
-999°F
Unit has alarms &
0 to -555°C
AL1 no
If AL1 = Pr: rL1 to A1HI
rL1
A1HI
If AL1 = dE: 0 to 999°F/
999°F
Unit has alarms &
0 to 555°C
AL1 no
If AL1 = Pr: A1LO to rH1
rH1
CAL1
-99 to 99°F/-55 to 55°C/-99 to 99Units 0
InP2
J, K (appears as H), E or
J or rtd or 0-5
Dependent on model
rtd or 0-5, 420, 010, 020
number information
rL2
Sensor range low to rH2
Low limit sensor type
Hardware is present
rH2
Sensor range high to rL2
High limit of sensor type
Hardware is present
HYS2
1 to 99°F/1 to 55°C/ 1 to 99 units
3°F
Hardware is present
AL2
Pr, dE or no
Pr
Hardware is present
A2LO
If AL2 = dE: 0 to -999°F/
-999°F
Hardware is present &
0 to -555°C/0 to -999 Units
AL2 no
If AL2 = Pr: rL2 to A2HI
rL2
A2HI
If AL2 = dE: 0 to 999°F/
999°F
Hardware is present &
0 to 555°C/0 to 999 Units
AL2 no
If AL2 = Pr: A2LO to rH2
rH2
CAL2
-99 to 99°F/-55 to 55°C/-99 to 99Units 0
Hardware is present
Setup
Table 2 -
Setup Mode
Parameters and
Descriptions.
Setup Mode
Use this page as a master copy for your Series 733/734 Setup mode parameters.
Do not enter any values here; make photocopies instead.