P o w e r D e f e n d e r 1 4 0 f o r W a t e r w a y P o o l P u m p M o t o r
I n s t a l l a t i o n a n d O p e r a t i o n M a n u a l
20
Each press of the
Scroll Up
or
Scroll Down
button increases or decreases the RPM in increments
of ten (10). Press and hold the
Scroll Up
or
Scroll Down
button for two (2) seconds to increase or
decrease the RPM in increments of 100. Press
MENU/ENTER
to save the changes. Press
START/PAUSE
to exit the menu option and return to the menu tree in
Navigation Mode
. Press
START/PAUSE
again to return to normal operations.
Note
: You cannot increase
Priming Speed
beyond the maximum allowable RPM rating for the
motor, or decrease the
Priming Speed
below the minimum allowable rating.
Temp Unit
You can configure the pump to display temperature readings in Fahrenheit or Celsius.
Press the
MENU/ENTER
button once to enter
Navigation Mode
. Press
Scroll Up
or
Scroll Down
to select the
Standard Settings
menu tree. Press
MENU/ENTER
to enter the menu tree. Press
Scroll Down
until you reach the Temp Unit screen. Press
MENU/ENTER
again to enter
Input
Mode
. Press
Scroll Up
or
Scroll Down
to toggle the temperature format. Press
MENU/ENTER
to
save the changes. Press
START/PAUSE
to exit the menu option and return to the menu tree in
Navigation Mode
. Press
START/PAUSE
again to return to normal operations.
Low Temp Monitor
The control monitors the ambient temperature of the pump. If the temperature falls below a specified
threshold, the pump begins cycling on and off to keep water from freezing in the pump.
If the pump is not currently running, the pump switches on for 30 minutes at 30% of the rated speed
of the motor. The pump then idles for 30 minutes. If at the end of 30 minutes the temperature is still
below the low temperature threshold, the cycle repeats itself. By default, this feature is disabled.
Press the
MENU/ENTER
button once to enter
Navigation Mode
. Press
Scroll Up
or
Scroll Down
to select the
Standard Settings
menu tree. Press
MENU/ENTER
to enter the menu tree. Press
Scroll Down
until you reach the Low Temp Monitor screen. Press
MENU/ENTER
again to enter
Input Mode
. Press
Scroll Up
or
Scroll Down
to toggle the setting. Press
MENU/ENTER
to save the
changes. Press
START/PAUSE
to exit the menu option and return to the menu tree in
Navigation
Mode
. Press
START/PAUSE
again to return to normal operations.
Low Temp Monitor
The Low Temp Monitor threshold is configurable between a range of 0° C to 10° C (32° F to 50° F)
.
Note
: This option is not available unless you
Enable
the Low Temp Monitor setting above.
Press the
MENU/ENTER
button once to enter
Navigation Mode
. Press
Scroll Up
or
Scroll Down
to select the
Standard Settings
menu tree. Press
MENU/ENTER
to enter the menu tree. Press
Scroll Down
until you reach the Low Temp Monitor threshold screen. Press
MENU/ENTER
again to
enter
Input Mode
. Press
Scroll Up
to increase the digit or
Scroll Down
to decrease the digit. Press
MENU/ENTER
to save the changes. Press
START/PAUSE
to exit the menu option and return to the
menu tree in
Navigation Mode
. Press
START/PAUSE
again to return to normal operations.
Remote Control
The RS-485 port allows you to connect an external controller. When connected, the UI no longer
controls the motor. Commands from the external controller takes priority. Other than enabling or
disabling Remote Control and possibly the Node ID, the UI plays no role in communication.