background image

   • DEFAULT setting for this option is set to configuration Page 1,#13
    •  This setting does not get reset by SYSTEM DEFAULT and can only change through this menu
   • TIMEOUT time for this screen is set for 1 minute before return to MAIN screen

  n

 

TEMPERATURE DISPLAY:

 this screen will display raw values of the 3 sensors S1, S2, and S3 reading

    •  The 3 values will display in Fahrenheit degrees only (even with Celsius display in the MAIN screen)
    •  The 3 values displayed are not truncated. For example, 73.67°F is displayed, and not 73°F like shown in the  
    MAIN screen
    •  The values will get updated every 5 seconds regardless of the heat related pump status
    •  Display screen will not timeout for 5 minutes

  n 

AUX BUTTON MAP:

 the auxiliary panel is a potential future addition panel for Spa Manufacturers. There is no  

    software in the auxiliary panel and the panel can have from one to six auxiliary buttons depending on the    
    manufacturing. Therefore this screen provides the ability for spa manufacturers to assign their specific button to a  
    specific function of the spa
    •  The user will select from AUX BUTTON 1 TO AUX BUTTON 6 for mapping
    •  Each button can be mapped to one specific device, like LIGHT, PUMP1 TO PUMP6, BLOWER, AND OPTION 1  
      TO OPTION 4
    •  The user can map 2 buttons to the same function if needed
    •  The controller will use this information and take appropriate action when there is an aux button pushed
    •  Default setting for this mapping is set to AUX1=LIGHT, AUX2=PUMP1, AUX3=PUMP2, AUX 

 

 

      4=BLOWER, AUX5=PUMP3, AUX6=PUMP4
    •  This setting does not get reset by System Default and can only change through this menu

  n 

HEATING SETUP:

 this screen allows the Spa installer person to set a condition that prevents a circuit breaker  

    trip. A typical circuit breaker can only handle a certain amperage before it is tripped. The setting in this menu allows  
    software to calculate and limit the number of pumps in high speed that the user can operate with the heater turn on.
    •  Pump High: to select total amperage for a pump on high speed
   • HEATER: to select which KW Heater is currently used in the system
   • RATING: to select what type of circuit breaker that user has in their location.
      · Selection of x16 amps is for Europe and will have a different rule. This will not allow Pump 1 in HIGH speed  
        with Heater on. Pump 2 to 6 on High speed will not affect the heater.
    •  Default setting for this option is set to Pump = 17amps; Heater = 5.5 KWatts; and Circuit breaker rating = 40  
      amps (Only allow one High speed pump on with heater on)
    •  The Heat setting set by the manufacturer will be saved in flash memory when the button is pressed and re  
    membered even if the system is powered off and on.
    •  This setting does not get reset by SYSTEM DEFAULT and can only change through this menu

  n 

OPTION TIMER SELECTION:

 this is a special feature for Waterways controller. In the majority of the configuration,  

    there is a spare connector available and unused. The optional timer is assigned to this output and this can only be  
    used if enabled by the manufacturer. Currently, this option is not mapped to any panel button (unless requested by  
    the manufacturer), therefore the user can control it through a programmable timer.
    •  User will select an option output from 1 to 4 depending on the configuration
    •  If the option is selected, the user can start using the feature through MENU > OPTION TIMER.
    •  Default setting for this is none.
    •  If the user changes configuration, this option will reset to none.
    •  This setting does not get reset by SYSTEM DEFAULT and can only change through this menu

Reviews: