7 3 Start-up data sheet
Site
Installer
Outdoor unit
serial No.
Hydraulic unit
serial No.
model
model
Refrigerant type
Refrigerant charge
kg
Checks
Operating voltage & current on outdoor unit
Compliance with positioning distances
L/N
V
Condensate evacuation correct
Electric connections / connections tightnees
No GAS leaks (unit ID No. : )
L/T
V
Installation of refrigeration connection correct (lenght : m)
Reading in HEATING operating mode
Compressor discharge temperature
°C
N/T
V
Liquid line temperature
°C
}
}
}
Icomp
A
Condensation
temperature
HP = bar
°C
sub-cooling
°C
Tank water output temperature
°C
ΔT condensation
°C
Tank water input temperature
°C
ΔT secondary
°C
Evaporation temperature
LP = bar
°C
}
}
}
Suction temperature
°C
Overheating
°C
Battery air input temperature
°C
ΔT evaporation
°C
Battery air output temperature
°C
ΔT battery
°C
Hydraulic system of hydraulic unit
Secondary system
Low temp. heating floor
}
Circulator brand
Type
LT Radiators
fan coils
Domestic hot water ; tank type
Estimated water volume of secondary system
L
Options & accessories :
Power supply for connected electric auxiliary
Room thermostat
Operation in cooling mode possible
Room thermostat radio
Location of room sensor correct
Remote control
Cooling kit
Wireless remote control
DHW kit
Details
2 zone kit
Control settings
Configuration type
Essential settings
Installation and operating manual "1532 - EN"
- 59 -
Air to Water Heat Pump