background image

10

 

 

                                                                                                                                                   

                                                                                                                                         

 

 

                                                                                                                                                   

                                                                                                                                         

Start Up Procedure

1.  Set time of day.

2.  Set a.m. or p.m. 

3.  Set water hardness in grains per gallon (gpg).

Note : 

If the water contains iron and / or manganese, multiply the total parts per million (ppm) by “four”

              (4) and then add to the grains per gallon (gpg) of hardness. Use this COMPENSATED HARDNESS 

              level when programming the regeneration frequency.

1.  Set regeneration day override if other than (7) days is desired. (This is particularly useful when iron is 

     being treated to prevent fouling of the resin.)

2.  Set regeneration time, if other than 2:00 a.m. is desired.

-Start Up Procedure-

- Disinfection -

For disinfection of your unit, please follow the Sani-System Procedure on the back of the packet provided.

1.  Advance control valve to BACKWASH (cycle 1) position and allow water to run to drain for 3 to 4 minutes.

Warning :

 Close valve on bypass prior to selecting the backwash position. After backwash position has 

                   been established, slightly open bypass to evacuate air from the media tank. Fully open valve 

                   when all air is depleted. This procedure will prevent media from being uplifted into control valve.

2. Advance control valve to BRINE REFILL (cycle 4) position and allow the brine tank to fill just over the salt 

    grid plate.

3. Advance control valve to BRINE & RINSE (cycle 2) and allow the control valve to draw water from the 

    brine tank until it stops. If no draw is observed, check tightness of brine line compression fittings.

4. Advance control valve to RAPID RINSE (cycle 3) position and let run to drain for 3 - 4 minutes.

5. Advance control valve to BRINE TANK REFILL (cycle 4) position and allow the control valve to automatical

    ly fill the brine tank.

Note :

 Control valve will advance to service position automatically.

- Filling The Brine Tank With Salt -

To expect a high level of performance and reliability, a salt manufactured specifically for water softeners 

must be used. Salt of this grade is virtually free from dirt and other particulates that would eventually cause 

the softener to malfunction. A pellet type salt is recommended, although any high quality water softener 

salt (such as solar salt) will suffice. If iron is present in raw water, use of iron inhibiting salt is recommended. 

The salt level will decrease after each regeneration cycle. Consequently, the salt compartment will need to 

be checked and replenished periodically.

1. Fill the salt compartment with water softener salt as described above. This will be approximately 150 

    pounds of salt. 

Warning : 

Do not fill salt above level of the brine well.

2. Close cabinet brine tank lid.

Summary of Contents for CD24

Page 1: ...Cabinet Softener Manual Installation Operation Manual...

Page 2: ...sembly Page 19 Bypass Assembly Page 20 Additional Information Page 21 Troubleshooting Page 23 Error Codes Page 25 Warranty Page 27 FCC Compliance Statement http www chandlersystemsinc com files FCC_Co...

Page 3: ...that attacks some plastic materials It is recom mended that Teflon tape be used to seal plastic Noryl threaded fittings Res Up The use of Res Up or any other resin cleaners is prohibited These cause d...

Page 4: ...ft water The surfaces of these beads are covered with sodium ions As hard water enters the mineral tank and comes into contact with the resin an exchange of ions takes place as dissolved Calcium and M...

Page 5: ...to back up of hot water DO NOT install the unit in an area of direct sunlight or where freezing temperatures may occur See Installation Diagrams for proper placement and plumbing connections Major Sys...

Page 6: ...6 Removal of Top Cabinet Lid PUSH CLIPS Installation...

Page 7: ...this occur Caution If sweat soldering copper pipe remember to always use lead free solder and flux cover bypass valve with wet rags to prevent heat damage to connections and control valve If using PV...

Page 8: ...line is advisable to keep the drain line full and assure correct flow during backwash Elbows or other fittings must be kept at a bare minimum Note Where the drain line is elevated above the control va...

Page 9: ...ill flash 2 To set the Time of Day press the Set Change button First digit will flash Example 12 00 To change digit value press the Set Change button To accept the digit value press the Menu Enter but...

Page 10: ...ine tank to fill just over the salt grid plate 3 Advance control valve to BRINE RINSE cycle 2 and allow the control valve to draw water from the brine tank until it stops If no draw is observed check...

Page 11: ...will bypass the softener and be untreated You should manually bypass the softener if 1 The outside lines do not bypass the water softener and water is to be used for lawn sprinkling or other similar u...

Page 12: ...To Fast Cycle thru regeneration First complete above 2 steps Note Press and hold the Set Change button for 3 seconds to advance to the next cycle step Fast Cycle is not necessary unless desired to man...

Page 13: ...el this feature Example Override every 7 days A 07 default setting or cancel setting A 00 Maximum is 29 3 Regeneration Cycle Step Times Steps 1 2 3 4 Example 3 10 The next 4 displays set the duration...

Page 14: ...the default password the first time you connect to it the app will ask you to enter the password After entering it the first time you should not need to enter it again unless it changes 3 BTLE Valve d...

Page 15: ...s in ORANGE with a set button can be changed For Filters Set Backwash Frequency This sets the amount of day between backwash cycles Change Time of Day Press SET to set time automatically based on devi...

Page 16: ...p Option 2 Touch any graph to enlarge and see details Enlarged graphs are able to be zoomed in by pinching with two fingers Enlarged graph shown below Regenerate Unit at Next Regen Time button This wi...

Page 17: ...27 11 20016X108 9 Power Flow Meter Motor 10 11 Ref Description Part Number Qty 1 Front Plate 20016X001 1 2 Encoder Wheel 20001X007 1 3 Cabinet Legacy Board Assembly 20016X101 1 4 Main Gear 21001X120 1...

Page 18: ...17X100 1 7 Drain Elbow 20017X266 1 8 DLFC Clip 20017X214 1 9 Brine Valve 20251X225 1 10 BLFC Assy 20001X228 1 11 Brine Line Ferrule 20251X305 1 REF DESCRIPTION PART NO QTY 12 Injector Cap Screw 20001X...

Page 19: ...20016X007 1 2 Resin Tank 30935X000 1 3 Brine Well Assembly 20016X008 1 4 Cabinet Cap 20016X009 1 5 Cabinet Lid 20016X010 1 6 Top Insert 20018X008 1 7 Front Insert 20018X009 1 8 Clear 3 8 Tubing 5ft 5...

Page 20: ...20 Bypass Assembly REF DESCRIPTION PART NO QTY 1 D15 Bypass 20017X283 1 2 1 NPT 90 Elbow Set 20017X284 1 1 2 1 20017X283 D15 Bypass 2 20017X284 1 NPT 90 Elbow Set...

Page 21: ...will now lift off easily 4 Put new powerhead on top of the valve Be sure the drive pin on main gear engages slot in drive yoke wide side of drive yoke upright must face to the left away from the motor...

Page 22: ...er at piston drive yoke Remove powerhead mounting screws The entire powerhead assembly will now lift off easily Remove piston retaining plate screws 4 Pull upward on end of piston rod yoke until assem...

Page 23: ...all times Clean it yearly Salt may be bridged If using a salt grid plate ensure refill water is over it Resin fouling Call dealer Find out how to con firm it Clean the resin and prevent future foulin...

Page 24: ...items listed in 1 Improper control valve programming Check and reset programming Plugged restrict drain line Clean drain line and or flow control button Injector and or screen is plugged Clean or repl...

Page 25: ...coder connection If the encoder is plugged in and snapped into place skip to step 2 below If encoder is disconnected reconnect it and cycle power to clear the error 2 Disconnect powerhead from valve b...

Page 26: ...to one of the following factors The electrical outlet is not powered or is switched off The power cable has come unplugged from the circuit board The power supply has come unplugged from your electric...

Page 27: ...ervice charges delivery expenses property damage administrative fees or any costs incurred by the purchaser in removing or reinstalling the water treatment equipment The Warranty does not cover any cl...

Page 28: ...28 710 Orange Street Ashland OH 44805 PH 419 289 1500 FAX 419 289 1515 www watersoftinc com 0622TV...

Reviews: