1-INTRODUCTION & IMPORTANT INFORMATION
IMPORTANT INFORMATION!
This Water Leak Detection System will not
provide protection unless it is set up and
commissioned as detailed in section 5
For correct and effective operation the following must be completed:
a)
Appoint a person responsible for:
i) Understanding how the system works, setting and monitoring the
parameters and keeping records accordingly
ii) Being aware of the implications of the alarm and the inability to
draw water should a shut off valve be fitted
b)
As water consumption will be unique to each installation it is
important to establish periods of high use and low use ie when
occupied or unoccupied, day or night, week or weekend etc.
c)
An initial water audit will establish the daily/weekly patterns of
water consumption. Further regular monitoring should be undertaken
to fully understand the overall usage including seasonal fluctuations,
plant watering, tank filling, vehicle cleaning etc.
d)
Following electrical & mechanical installation, the following
procedures must be undertaken:
i) Set Time & Date
ii) Set K factors for pulse meter M1
iii) Set High Flow times Monday to Sunday as per the audit
iv) Run the system for 1 week – see section 4
v) Enter maximum flow parameters for both HF & LF times using the
readings from the Peak Litres screen
e)
Reboot and the system is ready to run
Summary of Contents for WLDS-10 Mk3
Page 2: ...NOTES...
Page 18: ...9 WIRING DIAGRAM...