Step 3. Plan Your Water System

1. Using a Pressure Storage Tank and Pressure Switch

Your RO system will produce permeate (product water) at a pressure capable of pressurizing a bladder 

tank, though tank recovery time will be limited by the production rate of the membrane(s).  Rates of 

water production for Vectapure™ RSX II systems are, at maximum (feed water @<1000 TDS):

RSX II 350

           0.25 USG/min. (0.94 litres/min.)

RSX II 700

           0.50 USG/min. (1.88 litres/min.)

       

For many systems, this rate of recovery will be insufficient in periods of peak usage.  It will be 

necessary for you to provide product water storage in a non-pressurized tank from which you may re-

pressurize the water for delivery to your appliances or plumbing system.

!

TOUJOURS PERMETTRE À UN NOUVEL ADOUCISSEUR INSTALLÉ POUR PRÉTRAITER UN 

SYSTÈME OI DE DÉBUTER AU CYCLE RÉTROLAVAGE/RÉGÉNÉRATION/RINÇAGE.  UTILISEZ 

L’ADOUCISSEUR HORS DE LA LIGNE JUSQU’À CE QUE L’EAU DEVIENNE CLAIRE, AVANT DE 

L’UTILISER POUR FOURNIR DE L’EAU D’ALIMENTATION OI.  CETTE PROCÉDURE S’APPLIQUE 

AUSSI POUR LES NOUVELLES INSTALLATIONS DE LIT DE RÉSINE.  LA COULEUR 

PROVENANT DES NOUVEAUX LITS DE RÉSINE PEUT ENDOMMAGER OU ENCRASSER LA 

SURFACE DE MEMBRANE OI.

!

WATERITE DOES NOT RECOMMEND THE USE OF A GRANULAR/BLOCK CARBON CARTRIDGE 

IN THE PRE-TREATMENT FILTER HOUSINGS SUPPLIED, FOR THE PRIMARY REDUCTION OF 

CHLORINE.  IT WILL REQUIRE REPLACEMENT TOO OFTEN, LIMIT FLOW RATES AND LIKELY 

LEAD TO CHLORINE BREAKTHROUGH TO THE MEMBRANE ELEMENT.  WE RECOMMEND 

THAT THIS HOUSING BE RESERVED FOR 5-MICRON OR 1-MICRON SEDIMENT CARTRIDGES, 

FOR THE REDUCTION OF SUSPENDED PARTICULATE.

!

IF THE SYSTEM IS CONNECTED DIRECTLY TO A PRESSURE TANK, MAKE SURE THAT A 

CHECK VALVE IS INSTALLED ON THE PRODUCT WATER LINE BETWEEN THE MACHINE 

OUTLET AND THE PLUMBING SYSTEM PRESSURE SWITCH, TO ELIMINATE BACKPRESSURE 

ON THE MEMBRANE(S).  FAILURE TO DO SO WILL CAUSE PERMANENT DAMAGE TO THE RO 

MEMBRANE(S).

If a pressure tank and pressure switch is used, be sure that the pressure switch is capable of carrying 

the full load amperage of the pump motor.  For reference, the motor full load amperages are:

  

 

 

120VAC

 

RSX II 350  

5.1 A 

 

RSX II 700

  7.5 A

Consult your electrician to determine the proper sized breaker for your installation.  Other motor 

voltages are available as a factory option.  Consult with your dealer for availability and pricing. 

The pressure switch will be used to turn off the RO unit at the cut-off pressure and turn it on at the cut-

in pressure, in the same way one is used to control a water well pump.  Set the pressure switch to a 

maximum shut-off pressure of 50 psi. 

Summary of Contents for VECTAPURE RSX

Page 1: ...F RENCE ET DE GUIDE TECHNIQUE IL EST FORTEMENT RECOMMAND DE CONTACTER LE SERVICE TECHNIQUE DE VOTRE REPR SENTANT WATERITE ADVENANT LE CAS D UNE INTERRUPTION INATTENDUE OU BIEN D UNE APPARENTE D FECTU...

Page 2: ...se retrouver dans le tube Les mol cules des autres min raux et contaminants sont rejet es et vacu es de la surface de la membrane vers le drain Q Quel proc d le Syst me VectapureMC RSX II utilise t i...

Page 3: ...du syst me OI est lev e plus importante sera la quantit d eau produite par la membrane Votre unit VectapureMC RSX II est munie d une membrane s faible consommation nerg tique qui est con ue pour fonc...

Page 4: ...lisation continue ou lorsqu utilis avec des sources d eau non trait e Selon la qualit de l eau d alimentation votre membrane s devrait avoir une dur e de vie de 1 5 ans Des conditions d eau plus diffi...

Page 5: ...rovenir des eaux r siduelles ou de fuites d une fosse septique L eau r siduelle en surface contenant des fertilisants aura aussi une teneur lev e en nitrates La source des nitrates devra tre trouv e e...

Page 6: ...gmenter la dur e de vie de vos l ments de membrane am liorer la qualit de l eau produite et r duire le temps d entretien et de nettoyage consacr au syst me L importance des conditions de l eau d alime...

Page 7: ...rie CF Charbon Excelclear pH 5 5 9 5 Corrosion interne Incrustations calcaires dans l quipement Dommages la plomberie Remplacez la source d eau Ajustez le pH Contactez votre d taillant Activit organiq...

Page 8: ...E DOES NOT RECOMMEND THE USE OF A GRANULAR BLOCK CARBON CARTRIDGE IN THE PRE TREATMENT FILTER HOUSINGS SUPPLIED FOR THE PRIMARY REDUCTION OF CHLORINE IT WILL REQUIRE REPLACEMENT TOO OFTEN LIMIT FLOW R...

Page 9: ...h If the inlet bulkhead fitting to the non pressurized tank is below the maximum water level in the tank make sure that a check valve is installed in the product water line between the RO unit s outle...

Page 10: ...Filter Cartridge and Membrane s 1 Remove the filter housing bowl by turning counter clockwise with the housing wrench supplied Remove all protective wrapping from the 5 micron filter cartridge Insert...

Page 11: ...sure that they are in good condition and are secure in their seating grooves While the housing is disassembled clean all components thoroughly to remove any debris or scaling When re assembling make s...

Page 12: ...ntial septic field for receiving the RO waste water from Vectapure RSX II systems unless the field has a rated capacity in excess of the waste flow capacity If used to 24 hour capacity these systems w...

Page 13: ...ded for feed water of less than a TDS of 1000ppm By changing the DLFC the TDS range can be increased up to 2000ppm See spare parts for range and part numbers when ordering an alternate DLFC Make sure...

Page 14: ...PERIOD A Note on Recovery Rates Your Vectapure RSX II is designed to operate at a recovery rate percentage of product water to total water used at maximum of 60 for feed water of 1000 TDS and 35 40 fo...

Page 15: ...system pressure feed water TDS permeate TDS permeate flow rate and waste flow rate This will allow you to see any developing performance trends or alert you to system changes that will require you to...

Page 16: ...parts or repair service during the warranty period Read the document completely for warranty claim instructions Your Vectapure RSX II system comes with a limited one year warranty covering materials...

Page 17: ...housing leaking Tighten with housing wrench Inspect o rings for cuts or crimps Low System Pressure Clogged pre filter or fouled pre treatment Replace pre filter cartridges Low feed water pressure Chec...

Page 18: ...oduct Adapter O ring N70209 Membrane Housing End Cap O ring N70328 Pre Filter Housing O ring RKE0013HLB Black Max 2521 Membrane TFC LP BME2521SL Drive Pump 100 GPH APR3BZ Drive Pump 140 GPH APR4BZ Dri...

Page 19: ...II 350 2 0 USGPM minimum includes 20 safety factor RSX II 700 3 0USGPM minimum on 1000 TDS feed water Feed water must be available at a minimum of 40 psi and a maximum of 80 psi at the specified flow...

Page 20: ...WATERITE TECHNOLOGIES INC Unit 3 75 Meridian Drive Winnipeg Manitoba Canada R2R 2V9 204 786 1604 Fax 204 7863 1599 waterite waterite com www waterite com Vectapure RSX II Feed Water Quality Waterite...

Page 21: ...ide Calcium Chloride Iron Fluoride Potassium Bicarbonate Magnesium Sulphate Manganese Nitrate Sodium Phosphate Ammonium Silica Strontium OTHER Total Alkalinity Turbidity Total Dissolved Solids pH Temp...

Page 22: ...22 REGISTER YOUR PRODUCT ONLINE AT WATERITE COM OR FILL OUT THE INCLUDED PRE PAID SELF ADDRESSED POSTCARD...

Page 23: ...23 REGISTER YOUR PRODUCT ONLINE AT WATERITE COM OR FILL OUT THE INCLUDED PRE PAID SELF ADDRESSED POSTCARD...

Page 24: ...24...

Reviews: