CYCLE SEQUENCE 

CYCLE SEQUENCE instructions allows the setting of the order of 

the cycle. There are 9 cycles which can be arranged in any order. 

Later in this book the INSTALLER SETTINGS allow the setting of 

how long cycles will last. 

 

END must be used as the last cycle option.  The SERVICE cycle should only be used in brine prefill applications. 

 

 

If using upflow brine verify that the valve is configured as follows: 

1.   upflow piston is installed; and 

2.   injector is located in up hole and injector plug is in down hole. 

The following is an example of how to set a valve so that when regeneration is initiated BACKWASH occurs first, 

dn 

BRINE occurs second, RINSE occurs third, and FILL occurs fourth. 

 

  STEP 1CS  

 

 

 

 

 

 

 

 

 

 

 

 

  STEP 2CS  

 

 
 
 
 

  STEP 3CS  

 

 

 

 

 

 

 

 

 

 

 

 

  STEP 4CS  

 

 

 

 

 

 

 

 

  STEP 5CS  

 

 

 

 

 

 

 

 

 

 

 

 

 

  STEP 6CS  

 

 

Step 1CS –  Press NEXT and 

 

simultaneously for 3 seconds until SOFTENING or 

FILTERING appears on the display and release. If SOFTENING doesn’t appear, use the 

or

 

button to display it. Then press NEXT and 

 

again for 3 seconds and release. If 

screen in Step 2CS does not appear in 5 seconds the lock on the valve is activated. To 

unlock press

,

  NEXT 

, and SET CLOCK in sequence, then press NEXT and 

simultaneously for 3 seconds and release. 
Then press NEXT and 

again for 3 seconds and release. 

 

 

Step 2CS –  Press the 

or 

, buttons until BACKWASH 

appears. Press NEXT to go to Step 3CS. 

Press REGEN if you need to return to the previous step. 

 

 

 

 

 

Step 3CS -  Press the 

or 

 

buttons until dn BRINE 

appears. Press NEXT to go to Step 4CS. 

Press REGEN if you need to return to the previous step. 

 

 

 

 

 

Step 4CS -  Press the 

or 

 

buttons  until RINSE 

appears. Press NEXT to go to Step 5CS. 

Press REGEN if you need to return to the previous step. 

 

 

 

 

Step 5CS -  Press the 

or 

 

buttons until FILL 

appears. Press NEXT to go to Step 6CS. 

Press REGEN if you need to return to the previous step. 

 

 

 

 

 

Step 6CS -  Press the 

or 

 

buttons until END 

appears. Press NEXT to exit CYCLE SEQUENCE. 

Press REGEN if you need to return to the previous step. 

CYCLE OPTIONS 

BACKWASH 

DN BRINE 

FILL 

END 

RINSE 

UP BRINE 

SOFTENING OR 

FILTERING 

 

Summary of Contents for V3175-01

Page 1: ...ENT FOR REFERENCE PURPOSES AND TECHNICAL GUIDANCE IT IS STRONGLY RECOMMENDED THAT QUALIFIED DEALER SERVICE PERSONNEL BE CONTACTED IN THE EVENT OF AN UNKNOWN INTERRUPTION OF SERVICE OR APPARENT PRODUCT...

Page 2: ...nly the length of each regeneration cycle but also the order in which cycles steps of regeneration occur The following pages instruct how to set the treatment unit s sequence of cycles cycle times sal...

Page 3: ...potassium permanganate sodium hydroxide hydrochloric acid COMPATIBLE CHEMICALS sodium bisulfite sodium hydrosulfite chlorine chloramines GENERAL INSTRUCTIONS During operation the normal user displays...

Page 4: ...Once the valve has completed the immediate regeneration the valve will regenerate one more time at the pre set regeneration time...

Page 5: ...use the or button to display it Then press NEXT and again for 3 seconds and release If screen in Step 2CS does not appear in 5 seconds the lock on the valve is activated To unlock press NEXT and SET C...

Page 6: ...p 4S Select the time for the second cycle which in this example is dn BRINE using the or button Press NEXT to go to Step 5S Press REGEN if you need to return to previous step NOTE The display will fla...

Page 7: ...s using the button If value is set to NORMAL the regeneration will occur at the preset time on O the regeneration will occur immediately when the gallons capacity reaches 0 zero NORMAL on 0 the regene...

Page 8: ...er of days between regenerations is reached AUTO On O oFF Reserve capacity automatically estimated Regeneration occurs immediately when gallons capacity reaches 0 Time of regeneration is not allowed t...

Page 9: ...point to the center of the bypass The system is isolated from the water pressure in the plumbing system Untreated water is supplied to the building See Figure 2 3 Diagnostic Position The inlet handle...

Page 10: ...ectrical Use a 115 120V 60Hz uninterrupted outlet Current draw is 0 5 amperes A 15 ft power cord is furnished The plug in transformer is for dry locations only Batteries are not used 1 The distance be...

Page 11: ...h the drain connection on the control valve This will provide an adequate anti siphon trap Where the drain empties into an overhead sewer line a sink type trap must be used Run drain tube to its disch...

Page 12: ...ion 1 to 28 default 14 or set to oFF Press NEXT to go to step 4I Press REGEN if you need to return to previous step STEP 4I Next Regeneration Time hour Set the hour of day for regeneration using or bu...

Page 13: ...system runs through the steps automatically and will reset itself to provide treated water when the regeneration has been completed MANUAL REGENERATION Sometimes there is a need to regenerate before t...

Page 14: ...remaining option is used the following steps must be completed Step 1US Press the NEXT button until SALT appears in the display It does not matter if the SALT display alternates with the LBS REMAININ...

Page 15: ...dily to the drain without the presence of air restore power and momentarily press the REGEN button to advance the control to the BRINE position 5 Fully open the inlet bypass valve handle bypass is now...

Page 16: ...2x36 3 6 V3109 Drive gear cover 1 2 6 V3002CC Drive assy CC not shown V3186 Transformer 110V 12V 1 5 3 Piston Assembly Item No Part No Description Qty 1 V3005 Spacer stack assy 1 2 V3004 Drive cap ass...

Page 17: ...3010 1K K injector assy DARK GREEN not shown V3170 O ring 011 lower not shown V3171 O ring 013 upper The injector plug and the injector each use one lower and one upper o ring Note For a backwash only...

Page 18: ...01 DLFC Retainer assy 1 7 V3162007 0 7 DLFC for elbow One DLFC must be used if fitting is used V3162010 1 0 DLFC for elbow V3162013 1 3 DLFC for elbow V3162017 1 7 DLFC for elbow V3162022 2 2 DLFC for...

Page 19: ...105 O ring 215 1 9 V3190 065 6 5 gpm DLFC for 1 fitting One DLFC must be used if 1 fitting is used V3190 075 7 5 gpm DLFC for 1 fitting V3190 090 9 0 gpm DLFC for 1 fitting V3190 110 11 0 gpm DLFC for...

Page 20: ...2 O ring 135 2 9 V3155 O ring 112 2 10 V3156 O ring 214 2 90 Vertical elbow adapter assy for bypass valve not shown Part No V319101 Part No Description Qty V3151 Nut 1 quick connect 2 V3150 Split ring...

Page 21: ...V3151 Nut 1 Quick Connect 2 2 V3150 Split Ring 2 3 V3105 O Ring 215 2 Description Fitting 1 Brass Sweat Assembly Assembly Part No V3007 02 2 req d Item No 4 Fitting only Part No V3188 2 req d Descript...

Page 22: ...et to disengage the notches To reassemble seat the bottom of the drive bracket so the notches are engaged at the bottom of the drive back plate Push the top of the drive bracket towards the two latche...

Page 23: ...s with an o ring To remove the drive cap assembly use the Service Wrench V3193 or insert a to 5 16 flat bladed screwdriver into one of the slots around the top 2 of the drive cap assembly so it engage...

Page 24: ...of the assembly into the control valve body The assembly is properly seated when at least four threads are exposed approximately 5 8 Do not force the spacer stack assembly in The control valve body b...

Page 25: ...ire visible then a plug should be found in the meter location With the nut removed a slot at the top of the water meter is visible Twist a flat blade screwdriver in the slot between the control valve...

Page 26: ...lve caps Caution Since the handles can be pulled off they could be accidentally reinstalled 180 degrees from their correct orientation After completing any valve maintenance press and hold NEXT and RE...

Page 27: ...ation d Control set at on 0 d Check with regen time option in programming e Control set at NORMAL on 0 e Check with regen time option in programming 5 ERROR followed by a code number ERROR code 1001 U...

Page 28: ...unplugged a Connect transformer and PC board power b No power at outlet b Restore power c Broken drive gear or drive cap assembly c Replace gear or drive cap assembly d Defective PC board d Replace b...

Page 29: ...WATERITE INC Winnipeg MB Canada www waterite com...

Reviews: