ENVISION AIR COILS INSTALLATION MANUAL

General Installation Information

The Envision series encased and uncased coils are designed 
for upflow, horizontal, and bottomflow applications. The 
coils have a dry nitrogen holding charge and are equipped 
with brazing stub refrigerant connections for easy 
installation. Both models come equipped with a factory 
installed TXV.

The installer should read the installation manual supplied 
with the compressor section for refrigerant line set sizing, 
connection procedure, and other important information 
pertaining to the system installation.

The installer should:
1.  Make sure that the air delivery of the furnace is adequate
 

enough to handle the recommended CFM and allow for

 

pressure drop across the air coil, filter, and duct work.

2.  Where precise forming of refrigerant lines is required, a
 

copper tubing bender is recommended for small

 

diameter tubing.  One should avoid sharp bends and

 

contact of the refrigerant lines with metal surfaces.

3.  Refrigerant lines should be protected where they pass
 

through the raw edges of holes.

4.  Coil suction line must be insulated, as well as the field
 

constructed plenum used to enclose the uncased coil. 

 

Encased coils are manufactured with insulated cabinets.

5.  Coil must be level for proper condensate drainage.
6.  Seal the openings into the cabinet to reduce risk of
 

condensate blow off from the coil.

NOTE:  The installation of optional heating and cooling 
equipment must be properly sized and installed in 
accordance with the furnace manufacture’s specifications 
and recommendations . In some cases “heating only” 
furnace air circulators may have to be replaced with 
multispeed blowers to upgrade the air delivery (CFM) 
when an add-on coil is installed .  Refer to the Encased and 
Uncased Coil Specification table for recommended CFM 
across the coil and filters .

Model

NRAC026

NRAC036

NRAC048

NRAC060

NHAC060

BTUH

26,000

36,000

48,000

60,000

60,000

CFM

925

1,225

1,625

1,760

1,760*

Encased and Uncased Coil Specifications

Coil Installation for Encased Models

WARNING: Electric furnaces may be connected to 
more than one supply circuit .

The installer should:
1.  Disconnect all electrical power to the furnace.
2.  For the install of an encased coil, it might be necessary
 

to fabricate a plate to adapt the coil’s cabinet to the

 

furnace or air handler air discharge opening.

3.  Install the cabinet and level it as needed to allow proper
 

condensate drainage.

4.  Seal the enclosure as required minimizing air leakage.
5.  Connect the refrigerant lines as outlined in the
 

Refrigerant Lines section.

Coil Installation for Uncased Models

WARNING: Electric furnaces may be connected to 
more than one supply circuit .

The installer should:
1.  Disconnect all electrical power to the furnace.
2.  For the install of an uncased coil, it might be necessary
 

to fabricate a plate to adapt the coil’s cabinet to the

 

furnace or air handler air discharge opening.

3.  Install the coil and level it as needed to allow proper
 

condensate drainage.

4.  Make a plenum to enclose the coil or drop the duct
 

directly over the coil. 

5.  Seal the enclosure as required minimizing air leakage to
 

reduce risk of condensate blow off from the coils.

6.  Insulate the entire plenum assembly as needed.
7.  Connect the refrigerant lines as outlined in the
 

Refrigerant Lines section.

* NHAC060 CFM is dependent on desired capacity (see Hydronic Coil Performance tables in SP1603)

Summary of Contents for Envision NHAC026

Page 1: ...IM1618 09 09 Envision Air Coils Installation Manual Dimensional Data Installation Information Maintenance Geothermal Water Source Heat Pumps R 410A Refrigerant 2 5 Ton ENCASED UNCASED AIR COILS...

Page 2: ......

Page 3: ...AIR COILS INSTALLATION MANUAL Table of Contents Model Nomenclature 3 Initial Inspection 3 Safety Considerations 3 Dimensional Data 4 5 General Installation Information 6 9 Hydronic Models 10 11 Maint...

Page 4: ...nching cloth for brazing operations and have a fire extinguisher available NOTE Local codes and regulations take precedent over any recommendations by the manufacturer In addition to conforming to man...

Page 5: ...4 1 23 4 16 8 2 1 2 0 cm 52 8 66 0 73 9 2 2 2 2 1 9 48 3 61 2 59 4 42 7 5 3 5 1 Encased Models Refrigerant Water Connections Condensate Connections Miscellaneous J K L M N O P Q R S T U V W X Y Z AA A...

Page 6: ...ls A B C Suction Liquid Condensate D E F G H I J K L Width Depth Height Sweat Sweat FPT NRAC026 036U in 20 0 24 9 20 7 5 8 3 8 3 4 15 0 17 5 0 7 1 3 10 0 3 0 1 7 7 0 13 3 cm 50 8 63 3 52 6 1 6 1 0 1 9...

Page 7: ...ace air circulators may have to be replaced with multispeed blowers to upgrade the air delivery CFM when an add on coil is installed Refer to the Encased and Uncased Coil Specification table for recom...

Page 8: ...lications follow the steps shown below Remove all access panels Remove the A coil assembly 1 and the horizontal drain pan From the vertical upflow position rotate the top of the 2 cabinet 90 to the ri...

Page 9: ...NRAC036 5 8 OD 3 8 OD 3 4 OD 3 8 OD 3 4 OD 1 2 OD NRAC048 3 4 OD 3 8 OD 7 8 OD 3 8 OD 7 8 OD 1 2 OD NRAC060 7 8 OD 1 2 OD 7 8 OD 1 2 OD 1 1 8 OD 1 2 OD Encased and Uncased Refrigerant Line Sizing NOT...

Page 10: ...to a drain line pitched away from the unit a minimum of 1 8 per foot to allow the condensate to flow away from the coil A trap must be installed in the drain below the bottom of the pan to ensure fre...

Page 11: ...must be equipped with an expansion tank to allow room for the heated liquid to expand A system is considered closed when a check valve or backflow prevention valve is installed in the cold water pipe...

Page 12: ...on the coil Filter Maintenance The air filter installed with the system must be cleaned or replaced to obtain maximum performance They should be inspected monthly under normal operating conditions an...