ENVISION AIR COILS INSTALLATION MANUAL

Hydronic Models

The water heater and hydronic air handler must be located 
indoors and not subject to freezing temperatures. The water 
heater must be installed in accordance to local codes and 
its own installation instructions. The piping between the 
water heater and air handler should be kept to a minimum.  
Piping should be sized to allow for water velocities of 2’-4’ 
per second. At average water velocities, air bubbles should 
be carried along the piping to an air separator where they 
can be discharged from the system. Water velocities greater 
than 4’ per second could cause flow noise and should be 
avoided. If water lines pass through an unconditioned space 
they should be protected to prevent them from freezing.  
Valves should be installed to allow system isolation. All 
closed loop hydronic systems must be equipped with 
an expansion tank to allow room for the heated liquid to 
expand. A system is considered closed when a check valve 
or backflow prevention valve is installed in the cold water 
pipe upstream of the water heater.   

Once piping is complete all air must be purged from the 
water lines. There is a dole valve at the top of the hydronic 
coil header that can be opened to purge air from the coil.  
There is also a plug at the bottom of the hydronic coil 
header for draining the coil.

Plug for coil drainage. 

Dole valve for air purging

Typical Installation. See the Hydronic Application Guide for other applications

LOAD PUMP

Source IN

P/T Ports

P/T Ports

Ball Valve

Dielectric

Unions

Dielectric

Unions

WaterFurnace

HYDRONIC UNIT

WaterFurnace

ENCASED HYDRONIC COIL

*NOTE: A 30 PSI pressure relief valve
(Part No: SRV30) should be used in
hydronic applications.

1-1/2˝
FPT

Expansion

Tank

Air

Vent

Pressure

Gauge

30 PSI

RELIEF VALVE

Air

Separator

TO

DSH

FROM

DSH

Back Flow Preventer /

Pressure Relief Valve

Source OUT

GEO

STORAGE

TANK

P/T Ports

Summary of Contents for Envision NHAC026

Page 1: ...IM1618 09 09 Envision Air Coils Installation Manual Dimensional Data Installation Information Maintenance Geothermal Water Source Heat Pumps R 410A Refrigerant 2 5 Ton ENCASED UNCASED AIR COILS...

Page 2: ......

Page 3: ...AIR COILS INSTALLATION MANUAL Table of Contents Model Nomenclature 3 Initial Inspection 3 Safety Considerations 3 Dimensional Data 4 5 General Installation Information 6 9 Hydronic Models 10 11 Maint...

Page 4: ...nching cloth for brazing operations and have a fire extinguisher available NOTE Local codes and regulations take precedent over any recommendations by the manufacturer In addition to conforming to man...

Page 5: ...4 1 23 4 16 8 2 1 2 0 cm 52 8 66 0 73 9 2 2 2 2 1 9 48 3 61 2 59 4 42 7 5 3 5 1 Encased Models Refrigerant Water Connections Condensate Connections Miscellaneous J K L M N O P Q R S T U V W X Y Z AA A...

Page 6: ...ls A B C Suction Liquid Condensate D E F G H I J K L Width Depth Height Sweat Sweat FPT NRAC026 036U in 20 0 24 9 20 7 5 8 3 8 3 4 15 0 17 5 0 7 1 3 10 0 3 0 1 7 7 0 13 3 cm 50 8 63 3 52 6 1 6 1 0 1 9...

Page 7: ...ace air circulators may have to be replaced with multispeed blowers to upgrade the air delivery CFM when an add on coil is installed Refer to the Encased and Uncased Coil Specification table for recom...

Page 8: ...lications follow the steps shown below Remove all access panels Remove the A coil assembly 1 and the horizontal drain pan From the vertical upflow position rotate the top of the 2 cabinet 90 to the ri...

Page 9: ...NRAC036 5 8 OD 3 8 OD 3 4 OD 3 8 OD 3 4 OD 1 2 OD NRAC048 3 4 OD 3 8 OD 7 8 OD 3 8 OD 7 8 OD 1 2 OD NRAC060 7 8 OD 1 2 OD 7 8 OD 1 2 OD 1 1 8 OD 1 2 OD Encased and Uncased Refrigerant Line Sizing NOT...

Page 10: ...to a drain line pitched away from the unit a minimum of 1 8 per foot to allow the condensate to flow away from the coil A trap must be installed in the drain below the bottom of the pan to ensure fre...

Page 11: ...must be equipped with an expansion tank to allow room for the heated liquid to expand A system is considered closed when a check valve or backflow prevention valve is installed in the cold water pipe...

Page 12: ...on the coil Filter Maintenance The air filter installed with the system must be cleaned or replaced to obtain maximum performance They should be inspected monthly under normal operating conditions an...

Page 13: ...12 ENVISION AIR COILS INSTALLATION MANUAL Notes...

Page 14: ...13 ENVISION AIR COILS INSTALLATION MANUAL Notes...

Page 15: ......

Page 16: ...9 Manufactured by WaterFurnace International Inc 9000 Conservation Way Fort Wayne IN 46809 www waterfurnace com 2009 WaterFurnace International Inc 9000 Conservation Way Fort Wayne IN 46809 9794 Water...

Reviews: