23
5 SERIES 506A11 OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL
Add On Thermostats and Zoning
Description
Aurora ‘Base’
Aurora Advanced
TP32U03/04 - MonoChrome
Traditional Y1, Y2 Thermostat
Elite Stat with full English fault codes and alerts, traditional
Y1, Y2 thermostat. Not compatible with AWL.
Optional
Optional
TP32S01/02 -
Traditional Y1, Y2 Thermostat
Traditional Y1, Y2 thermostat. Not compatible with AWL.
Optional
Optional
TPCM32U03A/04A - MonoChrome
Communicating Thermostat
Elite Stat with full English fault codes and alerts,
communicating thermostat. Monochrome thermostat allows
instantaneous energy measurement only. Compatible with
AWL.
Optional
Optional
TPCC32U01 - Color Touchscreen
Communicating Thermostat
4.3 in. color touchscreen communicating thermostat with
full English fault codes and alerts. Color thermostat allows
instantaneous energy measurement and 13 month energy
usage history. Compatible with AWL.
Optional
Optional
IntelliZone2
24V Zoning
Compatibility
IntelliZone2
24V is a non-communicating zoning system
requiring Y1, Y2 signals that controls up to 4 zones (dual
capacity). For heat pumps without the optional AXB board.
-
Optional
(IntelliZone2
Preferred)
IntelliZone2
®
Zoning
IntelliZone2
®
is a communicating zoning system that includes
color main thermostat and up to 6 zones (with variable
speed, 4 zones (with dual capacity). There are multiple
thermostat options (MasterStat, TPCC32UO1, SensorStat,
ZoneStat, SensorStat-Remote). Compatible with AWL.
-
Optional
(IntelliZone2
Preferred)
Add On Control Feature Kits
(field or factory installed)
Description
Aurora ‘Base’
Aurora 'Advanced'
Geo Energy Monitoring Kit
Monitors realtime power consumption of compressor, blower,
aux heat and pump. Requires thermostat TPCM32UO3A,
TPCM32UO4A, or TPCC32UO1. AXB required.
-
Standard
Refrigeration Monitoring Kit
Monitors realtime pressures, temperatures, superheat, and
subcooling. AXB required.
-
Optional Sensor Kit
Performance Monitoring Kit
Monitors air and water temperatures, and water flow rate
and calculates heat of extraction/rejection. AXB required.
-
Optional Sensor Kit
Data Logging (AWL) Kit
Allows data logging of up to 12 months. AXB required. Can
also be temporarily installed.
-
Optional
HAN/Smart Grid Com
(AWL and Portal) Kit
Allows direct communication of the Aurora to Smart Meters,
HAN, and internet. AXB required.
-
Optional
AXB Kit
for flow center linking,
IntelliZone2
Added to 5 Series for key features of IntelliZone2
communication, Energy, Refrigeration, and Performance
monitoring.
Optional
(Field Kit)
Standard
Service Device
Description
Aurora ‘Base’
Aurora 'Advanced'
Aurora Interface and Diagnostics
(AID) Tool
Allows setup, monitoring and troubleshooting of any
Aurora Control.
NOTE:
Although the ABC has basic compatibility with all
Aurora, new product features may not be available on older
AID Tools. To simplify the basic compatibility ensure the
version of AID is at least the same or greater than the ABC
software version.
For Service
(Ver. 1.xx or greater)
For Service
(Ver. 2.xx or greater)
The Aurora Control System cont.