DOUBLE WALL CONNECTORS
Double wall chimney connectors may be substituted
for the shielded pipe provided it is UL/ULC listed for
a 9” clearance or less.
WALL PROTECTORS
Materials and products listed for the purpose of
reducing clearance to combustibles shall be
installed in accordance with the conditions of the list-
ing and the clearances may be reduced by the per-
centage reduction as stated in the wall shield of the
manufacturer’s instructions.
For clearance reduction systems using an air space
between the combustible wall and the wall protector,
adequate air circulation shall be provided by one of
the following methods:
1.
Adequate air circulation may be provided by
leaving all edges of the air protector open
with at least a 1” air gap.
2.
If the wall protector is mounted on a single
flat wall away from corners, adequate air cir
culation may be provided by leaving bottom
and top edges or only the side and top edges
open with at least a 1” air gap.
3.
Wall protectors that cover two walls in a cor
ner shall be open at the bottom and top
edges with at least a 1” air gap.
4.
All clearances shall be measured from the
outer surface of the combustible material to
the nearest point on the surface of the Erin
90 T/V & R/V disregarding any intervening
protection applied to the combustible
material.
When using a manufactured wall shield system
observe local building codes and by-laws.
CHIMNEY
The Waterford Erin 90 T/V & R/V is a radiant room
heater and must be connected to a chimney of the
proper size and type capable of providing an ade-
quate continuous draught of 0.04 wg minimum. It is
best to connect to a chimney of the same size as the
stove spigot. Connection to a larger size may result
in somewhat less draught. Do not connect to a
chimney serving another appliance.
Minimum chimney height is 14’ 10” from floor on
which stove is installed. An existing masonry chim-
ney should be inspected and if necessary repaired
by a competent mason or relined using an approved
relining system. The stove must be connected to a
chimney with a minimum continuous draught of
.04wg. Poor draught conditions will result in poor
performance.
Note:
Connection to type “B” Gas Vents approved
for connection to a certain gas burning appliance will
only result in a fire.
6