Waterco Fulflo Pressure Pump
TROUBLESHOOTING GUIDE
Waterco strongly recommends you have a qualified service technician service your pump. However,
many problems may be solved by consulting the table below.
SYMPTOM
POSSIBLE CAUSE
ACTION
Motor won’t
start or run
No power supply
Check for blown/ tripped fuses and replace/
reset.
Defective wiring
Check for damaged or corroded power cables.
Have an electrician replace.
Motor burnt out
Have technician replace.
Impeller jammed
Have a service technician inspect the unit.
Low voltage supplied to unit
Check with power company to ensure correct
voltage is being supplied.
Motor runs hot
and the automatic
overload trips out
Irregular voltage supply
Check voltage supplied to unit is within the limits
specified on the pump name plate.
Poor ventilation
Provide adequate ventilation.
Red “Failure”
LED glows
Air leak in suction pipe
Make sure all pipe joints are air tight. Re-prime
pump. Press “Restart”.
Pump will not prime
Add water slowly so as to expel air from the
pump and pipe system. Press “Restart”. Repeat
as necessary. Check suction pipe and foot valve
for leaks.
Foot valve stuck or
strainer clogged
Remove, repair and clean.
Water level below foot valve
Lower foot valve deeper into well.
PRESSURE TANK AIR CHARGE
To check the air pressure, proceed as follows:
1. Switch power off to pump
2. If on flooded suction close gate valve on tank outlet
3. Open a tap on discharge side of the pump and relieve all water pressure
4. Check the tank air charge with a tyre gauge and inflate if necessary
The Correct Air Pressure Settings are:
Waterco Fulflo Pressure Pump 30 and Fulflo Pressure Pump 50 – 200 kPa (29 PSI).
If the Waterco Limited pump is within the stated warranty period and you experience faults always
contact your supplier or the nearest Waterco Limited branch for advice. Failure to do this may void
the warranty. Refer to warranty documentation supplied with the pump.
All electrical work is to be carried out by a qualified electrician. Under no circumstances should you
attempt repairs on the electrical components of Waterco Limited pumps unless you are qualified to
do so.
!
WARNING
PUMP
LINE
Power On
On
Failure
Restart
Starting Up
Prime the pump as above. Open a tap on the delivery side. Switch on the power supply to the unit.
The green “Power On” LED will glow, indicating power is being supplied to the unit. The pump
will start running and the yellow “Pump On” LED will glow. Water will begin to flow from the open
tap. Close the tap and the pump will switch off when it has reached the correct pressure. Running
time will vary depending on the size of the pressure pack but should not be much longer than 2-3
minutes.
If the red “Failure” LED glows, make sure there are no leaks in the suction line. Ensure the pump is
primed by opening the priming cap and check that it is full of water. Press “Restart” and the pump
should start running again.
Once running, if the pump switches off for a short time and then starts up again, check that all taps
are closed and that there are no leaks in the suction or delivery pipes. If this problem continues
refer to the troubleshooting section. If the pump will not switch off after initial start up refer to the
troubleshooting section.
Figure 3: Control Panel
I
pg 07