Waterco Airflo Owner'S Manual Download Page 7

Waterco Spa Blowers

pg 03

Piping

When arranging the piping connections to the Blower, observe the following,

1.  50 mm (2”) Class 9 or higher PVC pipe should be used in the installation. Using smaller
     diameter pipe will place stress on the motor.

2.  Do not glue piping to the Blower.

3.  Avoid water traps when installing the piping as they will reduce the efficiency of the Blower 
     

(refer to Figure 5d on Page 8).

4.  Install pipe loops where necessary 

(refer to Figure 5c on Page 6)

.

5.  Horizontal pipes shall have a one (1) degree fall towards the Spa.

6.  Check Valves shall be installed when the Blower is used in a Spa Jet Installation 

(refer to  

     Figure 5a on Page 6)

.

7.  Keep the number of 90 degree elbows to a minimum. Where possible, use two (2) 45 degree
     elbows instead of a 90 degree elbow.

8.  Keep the length of piping between the Spa and the Blower as short as possible (length of 
     piping should not exceed 12 metres).

Care must be taken to ensure loose material or water (including rain) will not be sucked into the 
piping connected to the Inlet Port of the Inline Blower.  Failure to do so may result in serious damage.

!

CAUTION

Figure 3: Mounting Bracket

Figure 4: Inline Model blowers showing
possible locations of Mounting Brackets

Summary of Contents for Airflo

Page 1: ...oduct has been installed this manual must be given to the owner operator of this equipment This equipment must be installed and serviced by a qualified technician Improper installation can create elec...

Page 2: ...ower supply cord is damaged it must be replaced immediately by the manufacturer service agent or similarly qualified person in order to avoid hazard The power supply cord should be located and protect...

Page 3: ...ation or repairs should be carried out by the manufacturer service agent or a similarly qualified person in order to avoid hazards Work may only be performed on this product after disconnecting it fro...

Page 4: ...evel Installation 02 Below Water Level Installation 02 Piping 03 To Connect Piping to the Blower 04 Spa Jet Booster Installation 04 Additional Requirements Air Manifold Installation 04 Additional Requ...

Page 5: ...automatically restart once it has sufficiently cooled down Waterco Blowers are designed to meet the specifications set out in AS NZS 3136 MODELS Standard Model Airflo Whisperair Whisperair S The stan...

Page 6: ...nting the Blower are shown below Figure 2 Mounting the blower Switching the Outlet Port The blower is packaged with the Mounting Bracket in the base of the Blower and the Outlet Port in the side Assum...

Page 7: ...1 degree fall towards the Spa 6 Check Valves shall be installed when the Blower is used in a Spa Jet Installation refer to Figure 5a on Page 6 7 Keep the number of 90 degree elbows to a minimum Where...

Page 8: ...mm hole in the top of the loop to allow gas to escape A 1 0mm hole is also required as a drain hole to prevent any water from entering the Blower Spa Jet Booster Installation Additional Requirements R...

Page 9: ...E WATER TRAPS Drill 1 0mm Gas Escape Hole c BELOW WATER LEVEL INSTALLATION 700mm Place Loop as Close to Spa as Possible Drill 1 0mm Dia Drain Hole b AIR MANIFOLD INSTALLATION Run Pipe Above Water Leve...

Page 10: ...een the Button Flange and the Spa shell should be sealed with a silicone sealant NOTE The air tubing should never be exposed to direct sunlight and should preferably be buried alongside the pool pipin...

Page 11: ...g another device e g radio light etc into the power point and switch on to check power supply Motor burnt out Check water has not entered the Blower and burnt out the motor Incompatible air button and...

Page 12: ...ittingbourne Kent UK Tel 44 0 1795 521 733 Waterco France Saint Priest France Tel 33 4 72 79 33 30 Waterco USA Inc Augusta Georgia USA Tel 1 706 793 7291 Waterco Canada Longueuil Quebec Canada Tel 1 4...

Reviews: