30119-33 Rev. 1.8/04-14
TRANS
+
4-20 mA.
mA
AMMETER
AMMETER
NOTE: Connections for
checking transmitter
power supply voltage (24
VDC). Connect voltmeter
in parallel with circuit.
NOTE: Shield on transmitter
cable can be connected to
the ground screw on the
IN36-1.
115 VAC
PULSE
mA
4-20 mA. INPUT
J-10
RED
JUMPER
GREEN
IN48 TERMINAL STRIP
IN36-1 (24 V) POWER SUPPLY
INST.
+
GND
L2
L1
-
115 AC
-
N
G
TB-2
R
-
+
L1
L2
L
GREEN
WHITE
BLACK
GRAY
ORANGE
+
-
RED
GREEN
+
-
+
-
BLACK
PULSE OUTPUT
(OPTIONAL)
WHITE
NOTE: Connections for measuring the
amount of current flowing in the 4-20 mA
loop. There should be 4.0 mA with no water
flowing through meter and 20.0 mA at full
scale. Connect ammeter in series with circuit.
MAIN PCB
PEN 1
VOLT METER
TESTING TRANSMITTER OUTPUT AND POWER SUPPLY VOLTAGE
TR15/TR16 TRANSMITTER (4-20 mA OUTPUT)
WIRED TO A MODEL IN48 10” CHART RECORDER SOLD BEFORE 5/93
NOTE: Connections for checking
transmitter power supply voltage (24 VDC) Con-
nect voltmeter in parallel with circuit.
VOLT
METER
+
-
TRANSMITTER
POWER (24 VDC)
+
-
J-6
-
+
250 OHM RESISTOR
+ -
+
-
TR15/TR16 CIRCUIT CARD TERMI-
NAL STRIP
NOTE: Connections for measuring the amount of current flowing
in the 4-20 mA loop. There should be 4.0 mA with no water flow-
ing through meter and 20.0 mA at full scale. Connect ammeter
in series with circuit. If there is no current in the loop and the
power supply voltage is there, then the problem is possibly in
the communication lines or the transmitter circuit board.
TR15/TR16 CIRCUIT CARD TERMINAL
STRIP
PROCEDURES FOR CHECKING INOPERATIVE INSTRUMENT SYSTEMS
HAVING A TRANSMITTER WITH 4-20 mA
TESTING TRANSMITTER OUTPUT AND POWER SUPPLY VOLTAGE
TR15/TR16 TRANSMITTER (4-20 mA OUTPUT)
WIRED TO A MODEL IN41 10” CHART RECORDER
12