7
TIMER OPERATION
:
Set Time of Day
When the timer is In Service, push either the Set Up or Set Down button once to adjust the Time
of Day by one digit. Push and hold to adjust by several digits.
Manually Initiating a Regeneration
1. When timer is In Service, press the Extra Cycle button for five seconds to force a manual regeneration.
NOTE:
You will hear a click, indicating the valve will go into regeneration. There is a 10-second
delay until the motor starts to advance.
2. The timer reaches Regeneration Cycle Step #1.
3. Press the Extra Cycle button once to advance valve to Regeneration Cycle Step #2 (if active).
4. Press the Extra Cycle button once to advance valve to Regeneration Cycle Step #3 (if active).
5. Press the Extra Cycle button once to advance valve to Regeneration Cycle Step #4 (if active).
6. Press the Extra Cycle button once to advance valve to Regeneration Cycle Step #5 (if active).
7. Press the Extra Cycle button once more to advance the valve back to In Service
Timer Operation During Regeneration
In the Regeneration Cycle step display, the timer shows the current regeneration step number the
valve is advancing to, or has reached, and the time remaining in that step. The step number that
displays flashes until the valve completes driving to this regeneration step position. Once all
regeneration steps are complete, the timer returns to In Service and resumes normal operation.
Example:
Less than 10 Minutes Remaining
in Regen Step #1
Press the Extra Cycle button during a Regeneration Cycle
to immediately advance the valve to the next cycle step
position and resume normal step timing.
Start a Regeneration Tonight
With metered delayed timers, press the Extra Cycle button momentarily. The In Service indicator
dot flashes and starts a Regeneration tonight at the programmed Regeneration Time.
Day Regeneration Timer
During normal operation the Time of Day display is visible at all times. The timer operates normally
until the number of days since the last regeneration reaches the Regeneration Day Override setting.
Once this occurs, a regeneration cycle is initiated at the preset Regeneration Time.
Flow Meter Equipped Timer
During normal operation the Time of Day display alternates with the Volume Remaining display
(gallons or m3).
— As treated water is used, the Volume Remaining display counts down from the calculated
system capacity to zero or (----). When this occurs a Regeneration Cycle begins or delays
to the set Regeneration Time.
— Water flow through the valve is indicated by the Flow Dot that flashes in a direct relationship
to flow rate.