Water Heater Innovations 196284-001 Instructions Manual Download Page 9

9

         

THERMOSTAT FOR NATURAL AND PROPANE GASES

FIGURE 6.

GAS PRESSURE REGULATOR

The gas pressure regulator is built into the gas valve and is
equipped to operate on the gas specified on model and rating
plate.  The regulator is factory adjusted to deliver gas to burner at
correct water column pressure allowing for a nominal pressure
drop through the controls.

The minimum gas supply pressure for input adjustment must not
be less than 5.0" W.C. (1.24 kPa) for natural gas and 11.0" W.C.
(2.74 kPa) for propane gas.

Do not subject the combination gas valve to inlet gas
pressures of more than 14.0" W.C. (3.48 kPa).  A service
regulator is necessary if higher gas pressures are encountered.

Gas pressure specified in Table 2, refer to flow pressure taken at
pressure tap of automatic gas valve while heater is operating.

OPERATION

It is recommended that a qualified person perform the initial firing
of the heater.  At this time the user should not hesitate to ask the

individual any questions which he may have in regard to the
operation and maintenance of the unit.

 

WARNING

DO NOT ATTEMPT TO OPERATE WATER HEATER WITH COLD
WATER INLET VALVE CLOSED.

NEVER OPERATE THE HEATER WITHOUT FIRST BEING CERTAIN IT
IS FILLED WITH WATER AND A TEMPERATURE AND PRESSURE
RELIEF VALVE IS INSTALLED IN THE RELIEF VALVE OPENING OF
THE HEATER.  DO NOT ATTEMPT TO OPERATE HEATER WITH COLD
WATER INLET VALVE CLOSED.

TO OPERATE THE WATER HEATER

1. Close the heater drain valve by turning handle clockwise 

.

2. Open a nearby hot water faucet to permit the air in the system

to escape.

3. Fully open the cold water inlet pipe valve allowing the heater

and piping to be filled.

4. Close the hot water faucet as water starts to flow.

5. The heater is ready to be operated.

A checklist is included in the SERVICE INFORMATION section of
this manual.  By using this checklist the user may be able to make
minor operational adjustments and save himself unnecessary
service calls.  However, the user should not attempt repairs which
are not listed in this section.

PURGING

Gas line purging is required with new piping or systems in which
air has entered.

 

CAUTION

PURGING SHOULD BE PERFORMED BY PERSONS EXPERIENCED
IN THIS TYPE GAS SERVICE.  TO AVOID RISK OF FIRE OR
EXPLOSION, PURGE DISCHARGE MUST NOT ENTER CONFINED
AREAS OR SPACES WHERE IGNITION CAN OCCUR.  THE AREA
MUST BE WELL VENTILATED AND ALL SOURCES OF IGNITION
MUST BE INACTIVATED OR REMOVED.

TABLE 2.

MANIFOLD PRESSURE SETTING

Model

Type of

                          Manifold

Number

Gas                                         Input

                           Pressure

***-75

Natural

75,100  Btu/hr

22 kW

4.0 in. W.C.

1.0 kPa

***-75

Propane

75,100  Btu/hr

22 kW

10.0 in. W.C.

2.5 kPa

***-100

Natural

75,100  Btu/hr

22 kW

4.0 in. W.C.

1.0 kPa

***-100

Propane

75,100  Btu/hr

22 kW

10.0 in. W.C.

2.5 kPa

Summary of Contents for 196284-001

Page 1: ...ned Tank Type Water Heater PART NO 196284 001 INSTALLATION OPERATION SERVICE MAINTENANCE Thank you for buying this energy efficient water heater We appreciate your confidence in our products CAUTION T...

Page 2: ...rity having jurisdiction In the absence of local codes the installation must comply with the latest editions of the National Fuel Gas Code ANSI Z223 1 NFPA 54 This publication is available from the Ca...

Page 3: ...nting 12 13 High Temperature Limit Switch 13 SERVICEINFORMATION 13 14 Pilot and Main Burner 13 Checking Gas Input 13 14 Vent System 14 Relief Valve 14 Hot Water Odor 14 Anode Rod Inspection 14 Winter...

Page 4: ...ter heaters Your commercial water heater meets or exceeds the ASHRAE IES 90 1b 1999 standards with respect to insulation and standby loss requirement making an insulation blanket unnecessary WARNING S...

Page 5: ...the original rating Therefore to calculate the input rating at 4000 feet 1219m 4 x 0 04 x 75 100 Btu Hr 12 016 Btu Hr 3 5 kW 75 100 Btu Hr 22 0 kW 12 016 Btu Hr 3 5 kW 63 084 Btu Hr 18 5 kW At 6000 fe...

Page 6: ...out bypass is installed in the cold water line between the water heater and street main or well Excessive pressure may develop in such closed systems causing premature tank failure or intermittent rel...

Page 7: ...l code authority may have other specific relief valve requirements ADRAIN LINE MUST BE CONNECTED TO THE RELIEF VALVE TO DIRECTDISCHARGETOASAFELOCATIONTOAVOIDSCALDING ORWATER DAMAGE THIS LINE MUST NOT...

Page 8: ...TBECHECKEDFORSAFE OPERATION MAKE SURE THAT THE OUTSIDE VENTS ON THE SUPPLY REGULATORS AND THE SAFETY VENT VALVES ARE PROTECTED AGAINST BLOCKAGE THESEARE PARTS OF THE GASSUPPLYSYSTEM NOTTHEHEATER VENTB...

Page 9: ...RESSURE RELIEF VALVE IS INSTALLED IN THE RELIEF VALVE OPENING OF THEHEATER DONOTATTEMPTTOOPERATEHEATERWITHCOLD WATERINLETVALVECLOSED TO OPERATE THE WATER HEATER 1 Close the heater drain valve by turni...

Page 10: ...gas supplier If the pilot will not stay lit after several tries turn the gas control knob to OFF Figure A and call your service technician or gas supplier 9 Replace inner and outer burner doors 10 At...

Page 11: ...n or gas supplier If the pilot will not stay lit after several tries turn the gas control knob to OFF Figure A and call your service technician or gas supplier 9 Replace inner and outer burner doors 1...

Page 12: ...er temperatures produced at various thermostat dial settings Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the thermostat setting by...

Page 13: ...T GAS COMPONENTS WEAR OUT OVER A PERIOD OF TIME THE GAS CARRYING COMPONENTS OF THIS APPLIANCE SHOULD BE INSPECTED FOR PROPER OPERATION PERIODICALLY BY A QUALIFIEDSERVICETECHNICIAN PILOT AND MAIN BURNE...

Page 14: ...ERHEATING OCCUR OR THE GAS SUPPLY FAILTO SHUTOFF TURNOFFTHEMANUALGASCONTROLVALVETOTHE APPLIANCE HOT WATER ODOR On occasion hot water may develop a strong odor If this occurs drain the heater completel...

Page 15: ...cids are not recommended for use on glass lined tanks CAUTION Observe handling instructions on label of product being used TANK CLEANOUT PROCEDURE The following practices will ensure longer life and e...

Page 16: ...orously dissolved by the UN LIME it can be reused if not the UN LIME should be replaced CHECKLIST Before contacting your dealer check the water heater to see if the apparent malfunction is caused by s...

Page 17: ...supply pipe at the heater see Figure 4 page 7 Close the valve which feeds water to the cold water inlet at the top of the heater Contact your dealer WATERHEATERMAKESSOUNDS 1 Occasional excessive conde...

Page 18: ...18 NOTES...

Page 19: ...19 NOTES...

Page 20: ...20...

Reviews: