Water Heater Innovations 196284-001 Instructions Manual Download Page 16

16

Prepare the Water Heater
To delime the water heater using the Flo-Jug method, first prepare
the heater for deliming.  Then install the long plastic male adapter
fitting into the drain valve opening of the water heater.  Use teflon
tape and hand tighten only.  Do not overtighten.

Prepare the Up-N-Down Transfer Kit
The next step is the preparation on the Up-N-Down Transfer Kit, if
you have not already done so:

1.

With the 5 gallon Up-N-Down container in the vertical position,
unscrew the plastic vent cap in the handle and pierce the plastic
membrane over the vent boss under the cap to allow the
container to vent.

Note:

  If your container does not have the vent cap and vent

boss, drill a 3/16" (4.76mm) hole in the handle.  When you
have finished deliming you will be able to plug this drilled vent
with the stainless steel screw that is supplied with the kit.

2.

Remove the container's cap and cut the plastic membrane
located in the 3/4" IPT opening in the cap.  Take care to not
damage the threads.

3.

Find the 3/4" male adapter, apply teflon tape to the threaded
end and screw it into the 3/4" IPT opening in the cap.

4.

Put cap with male adapter back on the container and slide 3/4"
hose over end of male adapter and fasten in place using hose
clamp provided.

Delime using Flo-Jug Method
5.

Slide the hose clamp over end of hose and slide hose over the
male adapter in the water heater drain opening and secure in
place using hose clamp.

6.

Lift container to the "Pour" Position, see Figure 9, being careful
to keep the vent in the handle above the liquid level and pour
the UN•LIME into the heater.

7.

Lower container, you may have to place the container on its
empty carton to prevent the UN•LIME from flowing back into the
container.

8.

Let UN•LIME remain in the heater for 5 minutes and then lower
the container to the "Drain" Position, see Figure 9.

9.

Deliming activity is indicated by foaming on the surface of the
UN•LIME.  If there is deliming activity, repeat steps 6 thru 8.

Normally, lime removal will be completed within one hour.  Severe
build-up of lime may take longer than an hour to complete descaling.

Note:  To check UN•LIME for continued use, place some scale or
white chalk in a glass with a small amount of UN•LIME.  If the
material is vigorously dissolved by the UN•LIME, it can be reused;
if not, the UN•LIME should be replaced.

CHECKLIST

Before contacting your dealer, check the water heater to see if the
apparent malfunction is caused by some external fault.  Consulting
this checklist may eliminate the need for a repair call and restore
hot water service.

NOT ENOUGH OR NO HOT WATER

1.

Check to see if the pilot flame is lit.

To relight the pilot, follow the instructions on the heater or
in this manual.

Check to see if the main gas shutoff valve in the gas supply
pipe is partially closed or the water temperature dial is set
too low.

2.

Look  for leaking or open hot water faucets.  Check for excessive
usage.

3.

Your gas company can check the gas input to the heater to see
that it is correct.  An underfired heater will not produce hot
water at its normal recovery rate.

4.

If the heater was installed when incoming water temperatures
were warm, colder incoming temperatures will create the effect
of less hot water.

5.

The thermostat water temperature adjusting dial may be set
too low.

6.

If you cannot determine the cause of the problems, contact
your dealer.

WATER TEMPERATURE IS TOO HOT

1.

The thermostat water temperature adjusting dial may be set
too high.

2.

If lowering control setting does not reduce the water
temperature contact your dealer.

GAS SMELL AT THE HEATER

1.

Close the main shutoff valve in the gas supply pipe near the
heater, see fig. 4 on page 7.  The thermostat includes a gas
control (top knob) which can also be closed.

2.

Call your gas company.

WATER LEAKAGE IS SUSPECTED

1.

Check to see if the heater drain valve is tightly closed.

2.

The apparent leakage might be condensation.  In warm or
humid locations, condensation can accumulate and run from
within the heater or its piping.

When a water heater is first installed and filled, the bottom
of the tank might condense water.  The water accumulation,
if excessive, can drip into the floor shield.  Also, during
normal operation there may be occasions when large
quantities of water are drawn, chilling the tank bottom.  This
too can result in condensation.

Condensation, appearing in the vent pipe (water dripping
from draft diverter) during heater operation is evidence of
poor vent action.  Possible causes are too long a vent pipe
or improper chimney operation.

3.

If the leakage is from the temperature and pressure relief valve
or its discharge pipe, it may represent a normal condition.
However, see RELIEF VALVE section on page 14.  DO NOT

Summary of Contents for 196284-001

Page 1: ...ned Tank Type Water Heater PART NO 196284 001 INSTALLATION OPERATION SERVICE MAINTENANCE Thank you for buying this energy efficient water heater We appreciate your confidence in our products CAUTION T...

Page 2: ...rity having jurisdiction In the absence of local codes the installation must comply with the latest editions of the National Fuel Gas Code ANSI Z223 1 NFPA 54 This publication is available from the Ca...

Page 3: ...nting 12 13 High Temperature Limit Switch 13 SERVICEINFORMATION 13 14 Pilot and Main Burner 13 Checking Gas Input 13 14 Vent System 14 Relief Valve 14 Hot Water Odor 14 Anode Rod Inspection 14 Winter...

Page 4: ...ter heaters Your commercial water heater meets or exceeds the ASHRAE IES 90 1b 1999 standards with respect to insulation and standby loss requirement making an insulation blanket unnecessary WARNING S...

Page 5: ...the original rating Therefore to calculate the input rating at 4000 feet 1219m 4 x 0 04 x 75 100 Btu Hr 12 016 Btu Hr 3 5 kW 75 100 Btu Hr 22 0 kW 12 016 Btu Hr 3 5 kW 63 084 Btu Hr 18 5 kW At 6000 fe...

Page 6: ...out bypass is installed in the cold water line between the water heater and street main or well Excessive pressure may develop in such closed systems causing premature tank failure or intermittent rel...

Page 7: ...l code authority may have other specific relief valve requirements ADRAIN LINE MUST BE CONNECTED TO THE RELIEF VALVE TO DIRECTDISCHARGETOASAFELOCATIONTOAVOIDSCALDING ORWATER DAMAGE THIS LINE MUST NOT...

Page 8: ...TBECHECKEDFORSAFE OPERATION MAKE SURE THAT THE OUTSIDE VENTS ON THE SUPPLY REGULATORS AND THE SAFETY VENT VALVES ARE PROTECTED AGAINST BLOCKAGE THESEARE PARTS OF THE GASSUPPLYSYSTEM NOTTHEHEATER VENTB...

Page 9: ...RESSURE RELIEF VALVE IS INSTALLED IN THE RELIEF VALVE OPENING OF THEHEATER DONOTATTEMPTTOOPERATEHEATERWITHCOLD WATERINLETVALVECLOSED TO OPERATE THE WATER HEATER 1 Close the heater drain valve by turni...

Page 10: ...gas supplier If the pilot will not stay lit after several tries turn the gas control knob to OFF Figure A and call your service technician or gas supplier 9 Replace inner and outer burner doors 10 At...

Page 11: ...n or gas supplier If the pilot will not stay lit after several tries turn the gas control knob to OFF Figure A and call your service technician or gas supplier 9 Replace inner and outer burner doors 1...

Page 12: ...er temperatures produced at various thermostat dial settings Short repeated heating cycles caused by small hot water uses can cause temperatures at the point of use to exceed the thermostat setting by...

Page 13: ...T GAS COMPONENTS WEAR OUT OVER A PERIOD OF TIME THE GAS CARRYING COMPONENTS OF THIS APPLIANCE SHOULD BE INSPECTED FOR PROPER OPERATION PERIODICALLY BY A QUALIFIEDSERVICETECHNICIAN PILOT AND MAIN BURNE...

Page 14: ...ERHEATING OCCUR OR THE GAS SUPPLY FAILTO SHUTOFF TURNOFFTHEMANUALGASCONTROLVALVETOTHE APPLIANCE HOT WATER ODOR On occasion hot water may develop a strong odor If this occurs drain the heater completel...

Page 15: ...cids are not recommended for use on glass lined tanks CAUTION Observe handling instructions on label of product being used TANK CLEANOUT PROCEDURE The following practices will ensure longer life and e...

Page 16: ...orously dissolved by the UN LIME it can be reused if not the UN LIME should be replaced CHECKLIST Before contacting your dealer check the water heater to see if the apparent malfunction is caused by s...

Page 17: ...supply pipe at the heater see Figure 4 page 7 Close the valve which feeds water to the cold water inlet at the top of the heater Contact your dealer WATERHEATERMAKESSOUNDS 1 Occasional excessive conde...

Page 18: ...18 NOTES...

Page 19: ...19 NOTES...

Page 20: ...20...

Reviews: