17
5 SERIES 500A11 INSTALLATION MANUAL
Electrical Data
* With optional 1 hp ECM motor
** With optional IntelliStart
®
Rated voltage of 208/230/60/1
All fuses Class RK-5
HACR circuit breaker in USA only
Single Speed Unit with Variable Speed ECM Motor
Model
Rated Voltage
Voltage
Min/Max
Compressor
HWG
Pump
FLA
Ext
Loop
FLA
Blower
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
MCC
RLA
LRA
LRA**
018
208-230/60/1
197/253
10.4
6.7
33.5
n/a
0.4
5.4
4.0
16.5
18.1
20
022
208-230/60/1
197/253
14.0
9.0
48.0
17.0
0.4
5.4
4.0
18.8
21.0
30
030
208-230/60/1
197/253
20.0
12.8
58.3
21.0
0.4
5.4
4.0
22.6
25.8
35
036
208-230/60/1
197/253
22.0
14.1
73.0
26.0
0.4
5.4
4.0
23.9
27.4
40
036*
208-230/60/1
197/253
22.0
14.1
73.0
26.0
0.4
5.4
7.0
26.9
30.4
40
042
208-230/60/1
197/253
26.0
16.6
79.0
28.0
0.4
5.4
4.0
26.4
30.6
45
042*
208-230/60/1
197/253
26.0
16.6
79.0
28.0
0.4
5.4
7.0
29.4
33.6
50
048
208-230/60/1
197/253
31.0
19.8
109.0
38.0
0.4
5.4
4.0
29.6
34.6
50
048*
208-230/60/1
197/253
31.0
19.8
109.0
38.0
0.4
5.4
7.0
32.6
37.6
50
060
208-230/60/1
197/253
41.2
26.4
134.0
47.0
0.4
5.4
7.0
39.2
45.8
70
070
208-230/60/1
197/253
44.2
28.3
178.0
63.0
0.4
5.4
7.0
41.1
48.2
70
4/6/12
Single Speed Unit with 5-Speed ECM Motor
Model
Rated
Voltage
Voltage
Min/Max
Compressor
HWG
Pump
FLA
Ext
Loop
FLA
Blower
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
MCC
RLA
LRA
LRA**
022
208-230/60/1
197/253
14.0
9.0
48.0
17.0
0.4
5.4
4.1
18.9
21.1
30
030
208-230/60/1
197/253
20.0
12.8
58.3
21.0
0.4
5.4
4.1
22.7
25.9
35
036
208-230/60/1
197/253
22.0
14.1
73.0
26.0
0.4
5.4
4.1
24.0
27.5
40
042
208-230/60/1
197/253
26.0
16.6
79.0
28.0
0.4
5.4
7.6
30.0
34.2
50
048
208-230/60/1
197/253
31.0
19.8
109.0
38.0
0.4
5.4
7.6
33.2
38.2
50
060
208-230/60/1
197/253
41.2
26.4
134.0
47.0
0.4
5.4
7.6
39.8
46.4
70
070
208-230/60/1
197/253
44.2
28.3
178.0
63.0
0.4
5.4
7.6
41.7
48.8
70
4/6/12
** With optional IntelliStart
®
Rated voltage of 208/230/60/1
All fuses Class RK-5
HACR circuit breaker in USA only
Single Speed Unit with PSC Motor
Model
Rated Voltage
Voltage
Min/Max
Compressor
HWG
Pump
FLA
Ext
Loop
FLA
Blower
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
MCC
RLA
LRA
LRA**
012
208-230/60/1
197/253
7.7
4.9
25.0
n/a
-
5.4
0.6
10.9
12.2
15
018
208-230/60/1
197/253
10.4
6.7
33.5
n/a
0.4
5.4
1.1
13.6
15.2
20
022
208-230/60/1
197/253
14.0
9.0
48.0
17.0
0.4
5.4
1.2
16.0
18.2
25
022*
208-230/60/1
197/253
14.0
9.0
48.0
17.0
0.4
5.4
1.5
16.3
18.5
25
030
208-230/60/1
197/253
20.0
12.8
58.3
21.0
0.4
5.4
1.5
20.1
23.3
35
030*
208-230/60/1
197/253
20.0
12.8
58.3
21.0
0.4
5.4
2.8
21.4
24.6
35
036
208-230/60/1
197/253
22.0
14.1
73.0
26.0
0.4
5.4
2.8
22.7
26.2
40
036*
208-230/60/1
197/253
22.0
14.1
73.0
26.0
0.4
5.4
3.5
23.4
26.9
40
042
208-230/60/1
197/253
26.0
16.6
79.0
28.0
0.4
5.4
3.5
25.9
30.1
45
042*
208-230/60/1
197/253
26.0
16.6
79.0
28.0
0.4
5.4
4.6
27.0
31.2
45
048
208-230/60/1
197/253
31.0
19.8
109.0
38.0
0.4
5.4
3.5
29.1
34.1
50
048*
208-230/60/1
197/253
31.0
19.8
109.0
38.0
0.4
5.4
4.6
30.2
35.2
50
060
208-230/60/1
197/253
41.2
26.4
134.0
47.0
0.4
5.4
5.9
38.1
44.7
70
070
208-230/60/1
197/253
44.2
28.3
158.0
63.0
0.4
5.4
5.9
41.8
49.3
70
4/6/12
* With optional high static motor
** With optional IntelliStart
®
Rated voltage of 208/230/60/1
All fuses Class RK-5
HACR circuit breaker in USA only
Summary of Contents for 500A11