Programmable Outputs
The Pre-delivery outputs are defined as follow:
Alarm Type
Output
Panic Alarm
Output 1 - Pulse high for 2 seconds
Burglary Alarm
Output 2 - Pulse high for 2 seconds
Close Programmable Output Event
Open Programmable Output Event
Output 3 - Set High
Output 3 - Set Low
Fire Alarm
Output 4 - Pulse high for 2 seconds
Medical Alarm
Output 5 - Pulse high for 2 seconds
A relay must be used when any device requiring a current greater than 50mA is connected
to the programmable output. The programmable output is a current sink circuit with a
maximum output voltage of 13.6VDC and a maximum output current of 50mA.
Programmable outputs are primarily connected to trigger external device inputs but not to
drive external devices. The Watchguard Relay Board (P/N: WGAPARB) must be used for
connecting, LEDs, sirens, bus-wired peripherals, etc.
There are many locations and values for setting the programmable outputs. Please read
Installer Manual for more detailed information.
Optional Settings
Skip steps 9-11 if dailer is not installed
Step 9 - Setting Account Codes (Location 61 - Partition 1)
Input a 4-digit account number for the control centre.
Enter:
1479* 61* [ACCOUNT NUMBER]* #
Step 10 - Setting Phone Numbers (Location 51-54)
Up to 4 telephone numbers can be stored. Installers can press # to exit INSTALLER MENU at
anytime without having the need to set up all 4 phone numbers.
Enter:
1479* 51* [TELEPHONE NUMBER 1]*
52* [TELEPHONE NUMBER 2]*
53* [TELEPHONE NUMBER 3]*
54* [TELEPHONE NUMBER 4]*
# (exit INSTALLER MENU)