Start-Up

The following procedure may be used to check out the 
socket and wiring installation prior to plugging in and 
powering the CBC-802. This procedure will check for 
any grounding problem and prevent the control from 
being blown. To carry out this test, a digital voltmeter 
set to measure AC voltage with a range of 250 VAC is 
needed.

q

  1.  With the CBC-802 control still unplugged 

from the socket, apply the 120 VAC to the 
control socket.

q

  2.  Place one test lead of the meter to terminal 

1 (hot side of 120 VAC input power) 
and with the other test lead of the meter 
measure to the other terminals of the 
socket. 

q

  A zero volt reading should be observed between 

terminal 1 and all other terminals except 
terminal 5 which should measure the AC line 
voltage to the socket.

q

  A reading of other than (0) zero volts to any of 

the terminals (except 1 to 5) indicates some 
type of leakage or grounding condition 
and MUST be removed or the control will 
potentially be destroyed on power up.

q

  3.  Once test is complete, turn off AC power. 

6

5

4

3

7

8

1

2

ACV

Term 1-2  0V

Term 1-3  0V

Term 1-4  0V

Term 1-5  (line 

 

voltage 120V)

Term 1-6  0V

Term 1-7  0V

Term 1-8  0V

Note:

 Voltages other than zero indicates problems.

q

  4.  After completion of ground fault checks is 

done and power off to the control socket, 
insert the CBC-802 into the octal socket.

Note

: The socket is keyed, so control will only go in 

one way. 

q

  5.  With control installed in socket, apply power 

to the CBC-802. On power up, the brake 
output LED (Red) should be on, and the 
brake should be energized.

q

  6.  Cycle the control between clutch/brake 

channels and observe that the channel 
output lights switch between brake and 
clutch (Red LED to Green LED) and insure 
brake and clutch are energizing properly.

q

  7.  Start the machine and allow unit to cycle. 

Make any adjustment on anti-overlap 
potentiometer while machine is running. 
Adjust only enough to eliminate any 
interaction from one unit turning off and 
other unit turning on.

Note:

 If time delay is set too high, a delay between 

one unit turning off and other unit turning on will be 
noticed. This could cause loss of control in machine 
function momentarily.

q

  8.  This completes the installation of the CBC-

802.