Making Electrical Provision for the Heater
Installation step 2
Mark the heater position on the floor.
Calculate in square feet the size of the area to be heated.
Then, using the sizing guide on the opposite page, refer to
the space heating cable spacing and perimeter distances to
correctly fit your space heating cable into the space
available.
Using a fiber tipped pen, mark a start point as close as
possible to the power supply, but no further than 8 feet
from it using the sizing guide on the opposite page.
Mark all the outer corners of the heated area observing the
perimeter distances referred to in the sizing guide and join
the corners up to form a marked out perimeter.
Mark up the spacing intervals for the space heating cable
following the sizing guide.
The spacing between heater cables must be a
minimum of 2" apart, but not further than 4"
apart. At no time, should the space heating
cables be less than 2" from the wall.
Note: The entire heater must be kept on the
same level; do not lay the heaters on stairways
or up walls.
A
Measure up
B
Mark start point
C
Mark perimeter and spacing intervals
17