29 March 2021
Due to continued product improvement, Warmington Ind LTD reserves the right to change product specifications without prior notification.
All Dimension are in mm
………….
Copyright ©
27
PROCEDURE FOR THE TEST AND COMISSIONING OF YOUR DECORATIVE FIRE
Ensure Gas Supply and the Power Supply (caution 240V) to the Unit
•
Refer to Data Plate on this specification for settings. The Data plate is attached to the under carriage of
the Burner.
•
Remove front grate.
•
Loosen the Jet test point and attach manometer (digital is preferred). The test point is on the right hand
side of the gas burner, as shown below:
•
Light appliance, adjust to high flame setting and check pressure, adjust to low flame and check pressure.
NOTE: Any alterations to pressure is to be carried out by a Certified Gasfitter
•
If adjustments are necessary, remove the cap. The Pressure Adjustment screw and nut are on the front
side of the Gas Control Valve (shown in diagram
B
in this specification) and are
factory
set.
High Pressure Setting
: Set the modulator to maximum condition. Screw in
Nut A
to increase the outlet pres-
sure then screw nut A out to decrease the pressure to the desired settings. Use 10mm spanner.
Low Pressure Setting:
Turn off the power to the modulator (by disconnecting the modulator harness connec-
tion at the valve
-
see wiring) and keep nut A stationary. Use a screwdriver to screw in
Screw B
to increase the
pressure and screw it out to decrease the pressure. Carefully replace the modulator plastic cap.
WARNING:
To ensure the correct operation of the modulator it is necessary that the plastic cap is returned to
its original location.