2.2.4. Mounting of the Boiler to Wall and Selection of Installation Place

•   Mounting of the boiler to wall must be checked and ensured to be stable 

and safe.

•  The hanger plate and connection screws supplied with the boiler shall 

be mounted on a filled or semi-filled brick wall in accordance with the 
installation scheme, and shall not be used for other purposes.

•  In case any different materials are used for mounting, the warranty of the 

boiler shall be terminated.

•  If the wall to which the boiler is to be mounter is not brick, strength of the 

support system shall be checked.

•  The boiler shall be mounted on a fire resistant wall.
•  The boiler should be mounted so as the height of the hanger plate to be 

between 1,8-2,2 mm from the ground.

•  The boiler shall be mounted with gaps as minimum 30 cm above the 

ground, minimum 3 cm from both sides and minimum 90 cm from 
the front side where the installation area is limited, for allowing easy 
intervention of the service technician.

•  The boiler shall not be installed in areas which contain or may contain 

explosives, flammables and acid vapors.

•  It shall not be installed next to or above ovens, cookers, radiators or 

heaters.

•  Hermetic boilers can also be installed in cabinets, provided that minimum 

5 cm from each side is left.

•  If the boiler is to be mounted over the kitchen countertop or kitchen set, 

there shall be a minimum 50 cm distance under the boiler.

•  Due to possibility of water draining from the Safety Valve of the boiler 

after mounting, the outlet shall be connected to the drainage line. If this 
is not possible; do not place electronic appliances, and tools, parts and 
materials which may breakdown, be deformed or form rust.

•  Any furniture should not be placed under the boiler due to the reasons 

specified above.

•  Make sure that there are no liquids or inflammable materials in the 

immediate vicinity of the boiler.

•  It is necessary to leave a spesific distance 1.0  mt between the heating 

device and the building material containing combustible material even 
the maximum allowable temperature value of 85 °C in the rated heat 
capacity of the appliance is not exceeded.

Figure 6 

Boiler minimum dimensions in the cabinet *Minimum clearances required for 

servicing

2.2.5. Natural Gas Connection (Appliance Category I

2H

)

The boilers are designed to run on methane (G20) gas. Gas supply pipes 
shall be equal to or larger than 3/4"G boiler fittings. Prior to making the 
gas connection, a thorough internal cleaning shall be carried out to all fuel 

 420 mm 

 min.480 mm 

min.

30

mm

min.

30 

mm

 725 mm 

min.

300 mm

 288 mm 

900 mm 

min. 50 mm

 170 mm 

supply installation pipe furnishings as possible wastes may distort smooth 
operation and reliability of the boiler.  Ensure that the gas supplied by the 
mains line is of the type prescribed for the boiler (refer to the label on the 
boiler).

Also, in case of reduced pressure, the network dynamic pressure (methane 
or LPG) used for supplying the combi should be carefully controlled and 
will impact the boiler strength.  Ensure that gas valve connection is correct.  
Flammable gas supply pipe should be able to supply correct adequate 
gas amount to the boiler when the boiler is at full power and be projected 
and sized according to force and local gas company specification and 
instructions in order to guarantee the appliance efficiency. Connection 
system shall comply with the legislation in force.

2.2.6. Flammable Gas Quality

The boiler is designed to be used with pure fuel not containing any foreign 
substances; therefore, required filter systems must be available in the gas 
supply line (for ensuring purification of the fuel).

2.2.7. In Case of Using Bottled Gas

• 300 mmSS pressurized hood should be used for LPG.
• 500 mmSS hood should not be used.
• 370 mmSS pressurized hood should be used for Propane.
• Do not place tubes at cold places having risk of snow for preventing frost
during winter months.
• Do not place tubes in hot places containing ovens, fireplaces for 
preventing dangers!
• Do not make connection with single tube and use LPG collector set for
double, triple uses.
• The distance between the collector and tube should be maximum 125 cm.
• Copper pipe installation should not used for distances longer than 125 cm.
• Hose connection ends should be tightened with clamp and no other tools
should be used.
• Gas installation rules with use of LPG tank and industrial tubes should
comply with local standards and to be performed by expert installation
teams and certified by the company undertaking the construction. In case
of failing to fulfil these conditions, combi shall not be commissioned by
Warmhaus Authorized Services.

2.2.8. Heating and Domestic Hot Water Installations

Radiator and ground heating installation shall be configured in accordance 
with technical specifications of the TSE (Turkish Standards Institution) and 
MMO (Chamber of Mechanical Engineers), and according to the heat loss 
calculation. Radiator type and amount and ground heating installation pipe 
amount shall comply with the heat loss calculation.

•  The design pressure strength of the heating installation shall be minimum 

6 bar.

•  If the mains pressure is more than 6.5 bar, a pressure reducer must be 

fitted.

•  It is recommended to construct the radiator installation as double line 

and without using bends and joints as much as possible.

•  Strainer filter shall be installed in heating return and tap water (city 

network) intake line if a boiler is to be used.

•  An additional expansion tank with 50 liters capacity shall be used 

depending upon the volumetric capacity of the heating water of the 
heating circuit (closed circuit) and working temperature.

•  If room thermostat and thermostatic radiator valve are to be used 

together; thermostatic valve shall not be installed in radiators in the 
place where room thermostat is present.

•  Cross connection must be made for efficient functioning in radiators 

longer than 1,5 m.

•  Covers shall be used for radiator and domestic hot water wall passages 

and fixed with wall clamps to prevent expansions due to heating.

•  An external boiler shall be fitted to the boiler for supply of domestic hot 

water. In case of using domestic water boiler, the three-way valve and 
boiler sensor within the product accessories.

9

warmhaus.com

Summary of Contents for Enerwa Plus 2500 H

Page 1: ...WALL MOUNTED CONDENSING SYSTEM BOILERS INSTALLATION USER MANUAL EnerwaPlus2500H EnerwaPlus3000H EnerwaPlus3500H...

Page 2: ...EnerwaPlus 2500 H EnerwaPlus 3000 H EnerwaPlus 3500 H...

Page 3: ...s and Installation 13 2 5 SAMPLE INSTALLATION SCHEME 14 2 6 SAMPLE INSTALLATION SCHEME 15 REMOTE CONTROL CONTROL ACCESSORIES OPTIONAL 17 2 7 COMBI FLUE CONNECTIONS 18 2 7 1 Exhaust Gas Flue Pipe Set a...

Page 4: ...den to open The boiler must not be used by children younger 8 years or invalid persons without supervision These seals provide evidence that the replacement of bolts required for safe operation If the...

Page 5: ...ural Gas 20 mbar G20 Available Available Not Available AT CH CY CZ DK EE FI GR IT LT NO RO SE SI SK YES II 2E3B P Natural Gas 20 mbar G20 Available Available Not Available DE YES II 2ELL3B P Natural G...

Page 6: ...indows contact the gas emergency service 1 4 GAS LEAKAGES 187 NATURAL GAS EMERGENCY LINE HOW TO ACT IN CASE OF DETECTING NATURAL GAS ODOR DURINGEMERGENCIES INFORMATION You can visit web sites of local...

Page 7: ...ue outlet b 2 hanger screws c 2 Dowels IV Hanger Plate Figure 4 V Exhaust Gas Flue Set optional Figure 5 Figure 1 Installation scheme Figure 3 Hanger Plate and Connection Accessories Keep packaging ma...

Page 8: ...ith EN 12514 standard 2 2 2 Places where hermetic boilers cannot be installed Stairwells of buildings common aisles ventilation ducts garret attics emergency exit doors storage rooms and other similar...

Page 9: ...gas valve connection is correct Flammable gas supply pipe should be able to supply correct adequate gas amount to the boiler when the boiler is at full power and be projected and sized according to f...

Page 10: ...o provide the required flow rate for the radiator heating system depending on the critical line pressure loss Warmhaus recommends the pump complying with the European Energy Efficiency Directives ErP...

Page 11: ...r Bathroom Drainage Lower Level Installation and Servicing Min 19 mm Min 30 mm Drainage pipe with water and air insulation Maximum length of the outer pipe shall be 3 m Insert the drainage pipe at lea...

Page 12: ...ficiency Index EEI EN16297 3 Max delivery head in m at Q 0 25 m3 h Max volume flow H 1 11 m Max power consumption 0 20 6 90 m 2 5 m3 h 52 Max speed 5766 rpm Hydraulic operational areas ENERWA PLUS 250...

Page 13: ...erature changes sent to radiator installation outside Temperature Sensor is activated when connected as independent from the used room thermostat typology and functions together with room thermostats...

Page 14: ...0 mm 2 FLUE Figure 20 Enerwa Plus H Single Boiler with 1 High Temperature Zone Hot Water Storage Tank System Scheme Example INSTALLATION EQUIPMENT 1 Boiler 2 Gas Safety Solenoid Valve 3 Ball Valve 4...

Page 15: ...3 x 1 0 mm 2 2 Boiler Slave 1 Boiler Master 6 Boiler Slave INSTALLATION EQUIPMENT 1 Boiler 2 Gas Safety Solenoid Valve 3 Ball Valve 4 Gas Filter 5 Vibration Isolator 6 Condensate Water Siphon and Drai...

Page 16: ...eventual copies The content of this document is Bertelli Partners s r l s property You must not be copy or use it in whole or in part without a prior written consent by Bertelli Partn 0 MLC27 1 LT ZO...

Page 17: ...justment and display of the boiler fault code on the display and reset it There are 6 daily programs for heating and DHW heating Daily 6 program can be applied for adjusting heating and Domestic Hot W...

Page 18: ...installation of hermetic boilers shall be original Warmhaus flue sets and they shall be used by observing measurements and restrictions given in installation instructions In case of using exhaust gas...

Page 19: ...pressure in the common air duct by 25 Pa under the condition that n 1 boilers are running at maximum nominal heat input Qn max and 1 boiler at the minimum heat input allowed by the controls b combusti...

Page 20: ...er installation If one of the dimensions D E F G or H is 25mm then the remainder MUST be as shown in brackets in accordance with B S 5440 1 NOTE The distance from a fanned draught appliance terminal i...

Page 21: ...red with the external pipe For security purposes combi suction discharge flue should not blocked even temporarily 1 90 bend 2 Sealing gasket 3 Sealing gasket 4 Centering wire 5 Exterior flue pipe 6 In...

Page 22: ...e and exhaust pipes is 30 metres regardless from whether they are used for intake or exhaust Figure 41 Vertical flue set installation application Figure 42 Hermetic flue type installation sample Imple...

Page 23: ...see Table 1 It must not be sited above the flue pipe The flue and air pipes must extend by at least 40 mm from the wall surface Condensing boiler emit a visible plume of water vapour from the flue te...

Page 24: ...11 660 600013 60 100 Condensed Flue Extension L 500 mm 153 11 660 600014 60 100 Condensed Flue Extension L 1000 mm 153 11 660 600015 60 100 Condensed Flue Extension L 2000 mm 153 11 660 600016 60 100...

Page 25: ...092 80 Condensed Twin Flue Extension Pipe L 1000 mm 153 11 660 600093 80 Condensed Twin Flue Extension Pipe L 2000 mm 153 11 660 600094 80 Twin Flue Bend 90 153 11 660 600095 80 Twin Flue Bend 45 153...

Page 26: ...commendations are given in BS 5440 Pt 1 For IE recommendations are given in the current edition of I S 813 Domestic Gas Installations 2 If the terminal discharges onto a pathway or passageway check th...

Page 27: ...materials or products near the boiler The exhaust gas flue set is not blocked Room thermostat s or control device is at ON position if applicable Follow the procedure given below if you are not going...

Page 28: ...boiler operates only for domestic hot water in this mode if a boiler is fitted To switch to domestic water position 3 2 4 Resetting the Boiler Restart When the appliance shows fault blocking error pu...

Page 29: ...be limited to the maximum temperature value e g Maximum 47 C as your boiler will have been set to Low Temperature Operation by the Authorized Service Turning off the Boiler To turn off the boiler whi...

Page 30: ...e curves given below After connecting the Outside Temperature Sensor by means of the P04 parameter It is adjusted according to average outside temperature of your province This setting will be perform...

Page 31: ...Safety Thermostat intervention The boiler does not operate E07 error code blinks Insufficient water in the system Pump clogging Pump Failure Pump Equipment clogging 1 First restart the boiler by push...

Page 32: ...er radiators must be on 4 RESET the boiler and check if the problem is solved 2 Call Authorized service if the fault remains unsolved E 21 Delta Temperature Radiator Heating supply and Return TSP 82 v...

Page 33: ...rvice if fault remains unsolved E 78 Maximum regulating current value is reached The boiler does not operate E78 error code blinks Gas Supply Pressure Wearing or corrosion of electrode Mixing of flue...

Page 34: ...ved E 93 Failed to regulate combustion temporary The boiler does not operate E93 error code blinks Wearing or corrosion of electrode Mixing of flue gas with fresh air Clogging in the flue or incorrect...

Page 35: ...S This warranty provided by WARMHAUS does not include fixing or eliminating faults caused by use of the appliance for purposes other than intended use as well as the conditions specified below 1 Damag...

Page 36: ...perature C 25 47 25 47 25 47 Operating Pressure Maximum bar 3 3 3 Operating Pressure Minimum bar 0 5 0 5 0 5 Expansion tank useful volume bar 8 10 10 Pump pressure at 1000 l h flow rate mH2O 5 5 5 5 5...

Page 37: ...t output at 30 of rated heat output and low temperature regime 1 P1 kW 4 16 4 87 5 71 Seasonal Space Heating Energy Efficiency s 92 92 92 Useful efficiency at rated heat output and high temperature re...

Page 38: ...70 28 70 28 7 Minimum heat input Qn kW 3 75 3 59 3 75 t 80 60 Maximum heat output Pn kW 28 28 01 28 Minimum heat output Pn kW 3 5 3 5 3 3 B 23 B 23P B 33 C 13 C 33 C 53 C 63 C 83 C 93 C 103 2H G20 20...

Page 39: ...33 7 33 7 Minimum heat input Qn kW 4 35 4 35 4 35 t 80 60 Maximum heat output Pn kW 33 02 33 02 32 8 Minimum heat output Pn kW 4 1 4 1 4 1 B 23 B 23P B 33 C 13 C 33 C 53 C 63 C 83 C 93 C 103 2H G20 2...

Page 40: ...4 25 24 25 24 25 Minimum heat input Qn kW 3 5 2 8 3 5 t 80 60 Maximum heat output Pn kW 23 7 23 7 23 6 Minimum heat output Pn kW 3 0 2 5 3 3 B 23 B 23P C 13 C 33 C 53 C 63 C 83 C 93 C 103 2H G20 20 MB...