1.0 User Instructions
1.1
Goldbird Models
Thermostat Control
The recommended minimum thermostat setting is 65
°
C. Below this ‘cold water corrosion’
is likely to occur which can reduce the life of the heat exchanger and is not covered by
the boiler warranty. The boiler thermostat is adjustable from 52
°
C to 88
°
C.
Mains Indicator
The green mains lamp will be lit when there is power to the control box.
H/L Reset
The yellow H/L reset lamp will be lit when the boiler has overheated and tripped the
high limit thermostat, which then needs to be manually reset. If the high limit thermostat
continues to trip, contact Warmflow or your service engineer/technician. The manual
reset thermostat has a cut out point of 110
°
C.
Lock-Out
The red lock out lamp will be lit when the burner has failed to fire and can be reset by
pressing the illuminated red reset button on the burner control box.
1.2
Bluebird, Kabin Pak and Whitebird Models
The recommended minimum thermostat setting is 65
°
C (thermostat setting 1). If the
high limit thermostat operates it may be reset by removing the reset cover and pressing
the reset button. If the burner goes to lockout it can be reset by pressing the illuminated
red reset button on the burner control box. Combustible material must not be placed
on top of the boilerhouse models or on top of the burner cover as the temperature of
certain exposed components can occasionally reach 70
°
C. The boiler thermostat is
adjustable from 60
°
C to 90
°
C and the manual reset limit thermostat has a set point of
110
°
C.
1.3
Servicing
It is recommended that the boiler is serviced annually by an OFTEC registered engineer.
WARNING: No adjustments to externally situated boilers should be made where wet
weather conditions prevail. In such conditions there may be a risk of ingress of water
into the appliance, which could lead to component failure or electrocution.
1.4
Components – 50/70, 70/90, 90/120, 120/150, 150/200, 200/250
LIMIT THERMOSTAT
RESET BUTTON COVER
BOILER
THERMOSTAT
CONTROL
TOP LID
FLUE
BURNER
LOCKOUT LAMP
& RESET BUTTON
BAFFLES
BOILER CASING
BURNER COVER
BASE INSULATION
TOP LID
FLUE
BURNER
LOCKOUT LAMP
& RESET BUTTON
BURNER COVER
BASE INSULATION
BAFFLES
LIMIT THERMOSTAT
MANUAL RESET
BUTTON COVER
BOILER
THERMOSTAT
CONTROL
THERMOSTAT
BOILER
CASING
Bluebird
Goldbird/Whitebird
Page 2