background image

warema_2051514_alhb_en_v2•2022-07-01

We reserve the right to make technical modifications

4

Jumper 

6,3 AT H

250 V / 5x20mm

2 3

1

M∼

Motor 1

2 3

1

M∼

Motor 2

2

3

1

M∼

Motor 3

2

3

1

M∼

Motor 4

sun shading system

sun shading system

sun shading system

sun shading system

N

PE

N

PE

N

PE

N

PE

BU

GNYE

BK BN

BU

GNYE

BK BN

BU

GNYE

BK BN

BU

GNYE

BK BN

Bus A -

Bus B +

YCYM 2×2×0.8 mm 

Bus

Bus

0 V

Bus A -

Bus B +

0 V

to next bus device

2

PE

N

L

connecting line

230 V AC, 

50/60 Hz, 16 A, 

3 x 1.5 mm²

All bus lines 

from previous bus device 

Attention:

Only one motor can be connected 

per motor terminal set!

If interconnected, the motor 

will be damaged!

The total power (of all 4 outputs) 

per fuse must not 

exceed 1000 VA.

All motor lines 

H05-RR-F 4 G 0.75 BK, 

type WAREMA

All push button lines 

JY(St)Y 2×2×0.8 mm 

Max. line length 200 m 

for interference-proof routing, 

use a twisted paired line.

Fig. 5 

Connection example BACnet 4M230.8 AP

Summary of Contents for BACnet 4M230.8I AP

Page 1: ...annot be assumed the device must not be started or must be deactivated This assumption is justified if the housing or the connecting lines show signs of damage the device is no longer working ARNING W It is important to comply with the following points in the interest of personal safety Children may not play with the operating elements of the control unit or the remote control Store remote control...

Page 2: ...ed LED Communication error CRC ERROR Red LED Communication error Framing ER ROR Red LED Incomplete frames Red LED Input bridged Yellow LED Output active Yellow LED Maintenance There are no parts inside the device that require mainte nance In the event of a malfunction the built in miniature fuses should only be replaced by a certified electrician Liability Failure to comply with the product inform...

Page 3: ...age temperature 0 70 C Humidity not condensing 10 40 85 Frel Degree of soiling 2 Connection Connecting line Spring terminal U Contact Permissible line cross section max 2 5 mm Stripping length min 8 mm Motor outputs Spring terminals Permissible line cross section max 2 5 mm Stripping length min 8 mm Inputs Spring terminals Permissible line cross section max 2 5 mm Stripping length min 8 mm BACnet ...

Page 4: ...B YCYM 2 2 0 8 mm Bus Bus 0 V Bus A Bus B 0 V to next bus device 2 PE N L connecting line 230 V AC 50 60 Hz 16 A 3 x 1 5 mm All bus lines from previous bus device Attention Only one motor can be connected per motor terminal set If interconnected the motor will be damaged The total power of all 4 outputs per fuse must not exceed 1000 VA All motor lines H05 RR F 4 G 0 75 BK type WAREMA All push butt...

Reviews: