MOUNTING ON PIPES – IKV, IKF, KVI, KVD, KVM, KVR, KVI-B

Before mounting of the flap valve, make sure that the mounting surface of the inspection well or existing pipe is clean 

and smooth. Make sure the flap valve is intact and clean. 

When mounted the flap valve should not lean more than 5 degrees from horizontal in any direction. Violating this can 

result in reduced watertightness, blockage of moving parts and permanent damage to the flap valve.

IKV and IKF flap valve for direct plug-in into pipe installations are supplied as standard with two sets of sealing rings in 

different sizes to ensure proper sealing on pipes with variable tolerances.

For proper sealing, make sure to use the correct one.

SERVICE ACCESS 

To be able to perform proper repair and servicing of the flap valve, there must be an acceptable accessibility to reach 

the flap valve.

Summary of Contents for WAGATE KVI 110

Page 1: ...INSTALLATION MAINTENANCE PRODUCT GUARANTEE WAGATE FLAP GATES PLEASE NOTE SERIAL ORDERNUMBER HERE...

Page 2: ...U FOR PURCHASING A WAPRO PRODUCT FOR FURTHER PRODUCT INFORMATION PLEASE REFER TO WAPRO COM INDEX OPERATION INSTRUCTIONS 3 TRANSPORT AND STORAGE 3 STORAGE 4 MOUNTING 5 6 COMMISSIONING 7 MAINTENANCE 7 W...

Page 3: ...of any damage obtained during transport or storage Prior to first use the user needs to make sure that the steps described in the commissioning part of the manual have been followed precisely TRANSPO...

Page 4: ...ch types of operation is available If a flap valve is used outside its intended application proper function can t be ensured contact Wapro for advice WAFLAPTM FLAP VALVES DN OD NPS OD Made in Denmark...

Page 5: ...ased separately and follow the instructions for installation that are included Make sure to bolt through all mounting holes When mounted the flap valve should not lean more than 5 degrees from horizon...

Page 6: ...on Violating this can result in reduced watertightness blockage of moving parts and permanent damage to the flap valve IKV and IKF flap valve for direct plug in into pipe installations are supplied as...

Page 7: ...sed by other equipment To request warranty service the buyer should contact the WaGate dealer where the valve was purchased within a reasonable time after discovering any defects The valve serial numb...

Page 8: ...Rev 1 0 CONTACT WAPRO customerservice wapro com wapro com SE 46 0 454 185 10 DK 45 64 82 40 00 US 1 888 927 8677 UK 44 114 308 0123...

Reviews: