Installation, Servicing and User Instructions | EN
3.4.5 Terminal Locations
Dimension
Terminal Position
Distance (mm)
A*
Directly below an opening, air brick, opening window etc.
600
B
Above an opening, air brick, opening window etc.
300
C
Adjacent to an opening, air brick, opening window etc.
400
D
Below gutters, soil pipes or drain pipes
300
E
Below eaves
300
F
Below balconies or car port roof
600
G
From a vertical drain pipe or soil pipe
300
H
From an internal or external corner
600
I
Above ground roof or balcony level
300
J
From a surface facing the terminal
600
K
From a terminal facing the terminal
600
L
From an opening in the car port (e.g. door, window into the dwelling)
1200
M
Vertically from a terminal on the same wall
1500
N
Horizontally from a terminal on the same wall
300
P
From a vertical structure on the roof
600
Q
Above intersection with roof
150
* In addition, the terminal should not be nearer than 300mm to an opening in the building fabric
formed for the purpose of accommodating a built in element such as a window frame.