Maintenance
7URXEOHVKRRWLQJLQGLFDWLQJÀDPHRXWRYHUKHDW
The overheating thermostat has
activated and stopped the function
of the fuel pump.
Check that the device is not in after
cooling mode. After cooling mode
uses the same signal and it’s not
malfunction but a normal procedure.
(If it is a malfunction, after 5 minutes
the red signal (1) flashes in 30
seconds interval).
Check the amount of
ventilation air.
Red
Indicating flameout
The fuel has run out or its level is
too low for the intake hose in the
tank to reach it.
High wind pressure at the exhaust
lead-through fitting.
Water in the exhaust gas hose.
Water in the fuel.
The burner is sooted.
The fuel pump is broken.
The fuel needle is blocked.
Add fuel.
Ensure that the wind does not blow
directly in the lead-through.
Check the bends and loops of the
H[KDXVWJDVKRVHIRUZDWHU
(water trap).
Dewater the fuel or replace it.
5.1.3_en
Bring the device in for service.