Instruction & Technical Manual | 37
P006SFD
3/8
"
10
6
Simplex
504
281
92
14
31
20
11
3.6
P008SFD
3/8
"
14
8
Simplex
565
281
92
15
33
22
11
3.6
P010SFD
3/8
"
17
10
Simplex
635
281
92
16.5
36
25
11
3.6
P015SFD
3/8
"
26
15
Simplex
815
281
92
19.5
43
32
11
3.6
P022SFD
3/8
"
38
22
Simplex
1065
281
92
24
53
42
11
3.6
P033SFD
3/8
"
56
33
Simplex
1460
281
92
31
68
57.5
11
3.6
P044SFD
1/2
"
75
44
Duplex
1065
281
184
47
104
42
11
7.25
P066SFD
1/2
"
112
66
Duplex
1460
281
184
61
135
57.5
11
7.25
Standard pressure dewpoint
-40ºC (-40°F)
-70ºC (-100°F) with application of
flow correction factor
Min working pressure
4 barg (58 psig)
Max working pressure
16 barg (232 psig)
Electric controls
12VDC to 24VDC, 100VAC to 240VAC
Min inlet temperature
1.5ºC (35ºF)
Max inlet temperature
50ºC (122ºF)
Min ambient temperature
5ºC (41ºF)
Note: The temperature and pressure correction factors (below) should be applied to the above flow rates to suit the
application and ensure dryer performance. All flow rates are based on 7.0 barg (100 psig) and 35°C (95°F) at the dryer
inlet.
*Always use the pressure correction factor (PCF) closest to the actual inlet pressure condition
Operating pressure barg (psig)
4 (58)
5 (72)
6 (87)
7 (100)
8 (116)
9 (130) 10 (145) 11 (160) 12 (174) 13 (189) 14 (203) 15 (218) 16 (232)
Pressure correction factor (PCF)*
0.62
0.75
0.87
1
1.12
1.25
1.37
1.5
1.62
1.75
1.87
2.0
2.12
Temperature °C (°F)
20 (68)
25 (77)
30 (86)
35 (95) 40 (104) 45 (113) 50 (122)
Temperature correction factor (TCF)
1.07
1.06
1.04
1.00
0.93
0.78
0.64
Dewpoint °C (°F )
-40 (-40) -70 (-100)
Dewpoint correction factor (DCF)
1
0.7
SPECIFICATION
13. Dryer Sizing Table
Simplex dryer models are supplied with an A30XA pre-filter. Duplex models are supplied
with an A55XA pre-filter.
DRYER
PIPE
INLET FLOW RATE
DRYER
DIMENSION mm
WEIGHT
DIMENSION inch
MODEL
SIZE
Nm
3
/h SCFM
CONFI
A
B
C
Kg
lb
A
B
C
MODEL PO44SFD &
PO66SFD
B
A
C