30
Output Mode
Click on the radio buttons to manually control the alarm relay. The normal selection will be
Auto
,
where the WebAlert uses the various set points to open and close the relay. You can force the relay
open regardless of the presence of an alarm condition by selecting
Off
, or force the relay closed
regardless of the presence of an alarm condition by selecting
Hand
.
If you select Off, the alarm relay will not be triggered again until either Hand or Auto is selected, or
unless power to the unit is cycled off and on! If you select Hand, the relay will be closed until either
Auto or Off is selected, or until the Hand Time Limit (programmed in the next menu) expires.
The Off mode is handy to use as an alarm silence. The Hand mode is handy to be able to test the relay,
wiring, etc without needing to force an alarm condition.
Hand Time Limit
Type in the text box the maximum number of minutes that the alarm output can be activated in the
Hand mode. Any value between 0 and 1440 is acceptable. A value of 0 means the output can be left on
indefinitely.
Alarm Action Status
This menu is for information only, and displays the status of the remote alarm notification. The possible
messages to display are:
Alarm action completed:
The last alarm notification has already occurred and no further action
is pending.
Found new alarm:
A new alarm has occurred and no notification has yet occurred.
Alarm due in HH:MM:SS
The alarm delay time will be displayed with time counting down.
Taking action:
The alarm notification is about to occur.
Sending email:
If notification is via email, this will be displayed.
Alarm Action Log
Click the link to View Log File. The Alarm Action Log will tell you the status of any alarm emails that
may have been sent. It will show you the date and time of the alarm, the method of alarm notification,
whether it was successful at sending the message or not, and the type of alarm.
A window will open to ask if you would like to open the file or save it to disc. Select the method you
would like to use. The file is a basic text file with a .log extension that may be opened in any word
processing program (Word, Notepad, etc.).
Event Log
Click the link to View Log File. It will display the date and time of the alarm relay or any Generic Input
type digital input changing states.
Summary of Contents for WebAlert WA500
Page 9: ...6 Figure 1 Identification of Parts...
Page 10: ...7 Figure 2 Wiring Diagram for AC Power Input...
Page 11: ...8 Figure 3 Wiring Diagram for Digital Inputs and Outputs...
Page 12: ...9 Figure 4 Wiring Diagram for Analog Inputs DEVICES POWERED BY THE WEBALERT...
Page 13: ...10 Figure 5 Wiring Diagram for USB Devices and Communications...
Page 14: ...11 4 0 FUNCTION OVERVIEW 4 1 Front Panel Alarm LED Status LED...